Industrial Trading chervon right Manufacturers chervon right A chervon right ALLEN-BRADLEY chervon right 1734-OX2
About product Specifications Datasheet FAQ

ALLEN-BRADLEY 1734-OX2

Description

Allen Bradley 1734-OX2 Output Module - POINT I/O 2 Relay, 2.0 mA and bleed resistor thru snubber circuit @ 240V AC leakage curent

Part Number

1734-OX2

Price

Request Quote

Manufacturer

ALLEN-BRADLEY

Lead Time

Request Quote

Category

I/O Module

Specifications

Bounce Time

1.2ms (mean)

Conducted RF Immunity

10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Customer load to logic

250V continuous (Tested to 2550V dc for 1s), 250V continuous (Tested to 2550V dc for 1s)

Dimensions Inches(Millimeters)

2.21H x 0.47W x 2.97L(56H x 12W x 75.5L)

EFT/B Immunity

±2kV at 5kHz on signal ports

Emissions

CISPR 11; Group 1, Class A

Enclosure Type Rating

None (open-style)

ESD immunity

6kV contact discharges, 8kV air discharges

Expected Life of Electrical Contacts

Minimum 1,000,000 cycles resistive , 100,000 cycles inductive

Indicators

2 green/red module/network status, 2 yellow output status

Initial Contact Resistance

30m?

Isolation Voltage

Between any 2 sets of contacts

Keyswitch Position

7

Mass

1.30 oz/36.9 grams

Minimum Contact Load

5mA per point

Module Location

1734-TB or -TBS wiring base assembly

Off-State Leakage Current (max at 240V ac)

2.0mA and bleed resistor thru snubber circuit

Operate/Release Time

10ms max

Operational Temperature

-20 to 55°C (-4 to 131°F)

Output Current Rating (at rated power)Inductive

2.0A steady state @ 5-28.8V dc, L/R-7ms, 0.5A steady state @ 48V dc, L/R - 7ms, 0.25A

Output Current Rating (at rated power)Resistive

2A @ 5-28.8V dc, 0.5A @ 48V dc, 0.25A @ 125V dc, 2A @ 125V ac, 2A @ 240V ac

Output Signal Delay OFF to ON

10ms maximum (time from valid output on signal to relay

Output Signal Delay ON to OFF

10ms maximum (time from valid output off signal to relay deenergization by module)

Output Voltage Range (load dependent)

5-28.8V dc @ 2.0A resistive, 48V dc @ 0.5A resistive, 125V dc @ 0.25A resistive, 125V ac @ 2.0A resistive, 240V ac @ 2.0A resistive

Outputs per Module

2 Form C isolated (normally open; normally closed) electromechanical relays

POINTBus current

100mA max @ 5V dc

Power dissipation

0.5W max

Power Rating (steady state)

250W max. for 125V ac resistive output, 480W max. for 240V ac resistive output, 60W max. for 28.8V dc resistive output, 24W max. for 48V dc resistive output, 31W max. for 125V dc resistive output, 250VA max. for 125V ac inductive output, 480VA max. for 240V ac inductive output, 60VA max. for 28.8V dc inductive output, 24VA max. for 48V dc inductive output, 31VA max. for 125V dc inductive output

Radiated RF Immunity

10V/m with 1kHz sine-wave 80%AM from 80MHz to 1000MHz, 10V/m with 200Hz 50% Pulse 100%AM at 900Mhz

Relative Humidity

5 to 95% noncondensing

Shock

Operating:30g peak acceleration, Non-operating:50g peak acceleration

Storage Temperature

-40 to 85°C (-40 to 185°F)

Supply Current

2A per channel maximum, 4A per module

Surge Transient Immunity

±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports

Switching Frequency

1 operation/3s (0.3Hz at rated load) max

Terminal base screw torque

7 pound-inches (0.6Nm)

Thermal Dissipation

1.7 BTU/hr max

Vibration

Tested 5g @ 10-500Hz

Voltage Range

240V ac max

Datasheet

pdf file

allen bradley=1734-ox2=datashee-1276009864t.pdf

436 KiB

Extracted Text

Installation Instructions POINT I/O 2 Relay Output Module (Cat. No. 1734-OX2 Series C) 9 4 5 3 6 2 8 7 10 1 41825OX2 Description Description 1 1 6 RTB Removal Handle Mounting Base 2 Mechanical Keying (orange) 7 1 Removable Terminal Block (RTB) 3 Module Wiring Diagram 8 DIN Rail Locking Screw (orange) 4 Module Locking Mechanism 9 Slide-in Writable Label 5 Insertable I/O Module 10 Interlocking Side Pieces 1 Wiring Base Assembly consists of item 1) mounting base, 1734-MB and item 7) removable terminal block, 1734-RT or -RTS. POINT I/O is a trademark of Rockwell Automation DeviceNet is a trademark of ODVA, Inc. Publication 1734-IN587B-EN-P - March 2002 Module Status Network Status NODE: Relay Output 0 1 1734 OX2 2 POINT I/O 2 Relay Output Module This Series C product can be used with DeviceNet and PROFIBUS adapters. It can be used with ControlNet and Ethernet adapters using RSLogix 5000, version 11 (or higher) software. Important User Information Because of the variety of uses for the products described in this publication, those responsible for the application and use of these products must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. In no event will Allen-Bradley be responsible or liable for indirect or consequential damage resulting from the use or application of these products. Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication. Allen-Bradley publication SGI-1.1, Safety Guidelines for the Application, Installation and Maintenance of Solid-State Control (available from your local Allen-Bradley office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication. Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited. Throughout this publication, notes may be used to make you aware of safety considerations. The following annotations and their accompanying statements help you to identify a potential hazard, avoid a potential hazard, and recognize the consequences of a potential hazard. Publication 1734-IN587B-EN-P - March 2002 POINT I/O 2 Relay Output Module 3 Identifies information about practices or WARNING circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ! Identifies information about practices or ATTENTION circumstances that can lead to personal injury or death, property damage, or economic loss. ! Identifies information that is critical for IMPORTANT successful application and understanding of the product. Publication 1734-IN587B-EN-P - March 2002 4 POINT I/O 2 Relay Output Module Environment and Enclosure ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating. ! This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as "open type" equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, see the appropriate sections in this publication, as well as the Allen-Bradley publication 1770-4.1 ("Industrial Automation Wiring and Grounding Guidelines"), for additional installation requirements pertaining to this equipment. POINT I/O is grounded through the DIN rail to ATTENTION chassis ground. Use zinc plated, yellow chromated steel DIN rail to assure proper grounding. Using other DIN rail materials (e.g. aluminum, plastic, etc.) which can corrode, oxidize or are poor ! conductors can result in improper or intermittent platform grounding. Publication 1734-IN587B-EN-P - March 2002 POINT I/O 2 Relay Output Module 5 EXPLOSION HAZARD WARNING • Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous. • Do not disconnect connections to this equipment ! unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product. • Substitution of components may impair suitability for Class I, Division 2. • If this product contains batteries, they must only be changed in an area known to be nonhazardous. Preventing Electrostatic Discharge ATTENTION This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines ! when you handle this equipment: • Touch a grounded object to discharge potential static. • Wear an approved grounding wriststrap. • Do not touch connectors or pins on component boards. • Do not touch circuit components inside the equipment. • If available, use a static-safe workstation. • When not in use, store the equipment in appropriate static-safe packaging. Publication 1734-IN587B-EN-P - March 2002 6 POINT I/O 2 Relay Output Module Installing the Mounting Base To install the mounting base on the DIN rail, proceed as follows. 1. Position the mounting base vertically above the installed units (adapter, power supply or existing module. 2. Slide the mounting base down allowing the interlocking side pieces to engage the adjacent module or adapter. 3. Press firmly to seat the mounting base on the DIN rail. The mounting base will snap into place. 4. To remove the mounting base from the DIN rail, remove the module, and use a small bladed screwdriver to rotate the base locking screw to a vertical position. This releases the locking mechanism. Then lift straight up to remove. Installing the I/O Module The module can be installed before, or after base installation. Make sure that the mounting base is correctly keyed before installing the module into the mounting base. In addition, make sure the mounting base locking screw is positioned horizontal referenced to the base. When you insert or remove the module while WARNING backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous ! before proceeding. 1. Using a bladed screwdriver, rotate the keyswitch (2) on the mounting base clockwise until the number required for the type of module being installed aligns with the notch in the base. 2. Make certain the DIN rail locking screw is in the horizontal position. (You cannot insert the module if the locking mechanism is unlocked.) Publication 1734-IN587B-EN-P - March 2002 POINT I/O 2 Relay Output Module 7 3. Insert the module straight down into the mounting base and press to secure. The module will lock into place. Installing the Removable Terminal Block (RTB) A removable terminal block is supplied with your wiring base assembly. To remove, pull up on the RTB handle. This allows the mounting base to be removed and replaced as necessary without removing any of the wiring. To reinsert the removable terminal block, proceed as follows. When you connect or disconnect the Removable WARNING Terminal Block (RTB) with field side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. ! Be sure that power is removed or the area is nonhazardous before proceeding. 1. Insert the end opposite the handle into the base unit. This end has a curved section that engages with the wiring base. 2. Rotate the terminal block into the wiring base until it locks itself in place. 3. If an I/O module is installed, snap the RTB handle into place on the module. Publication 1734-IN587B-EN-P - March 2002 8 POINT I/O 2 Relay Output Module Removing a Mounting Base To remove a mounting base, you must remove any installed module, and the module installed in the base to the right. Remove the removable terminal block (if wired). 1. Unlatch the RTB handle on the I/O module. 2. Pull on the RTB handle to remove the removable terminal block. When you connect or disconnect the Removable WARNING Terminal Block (RTB) with field side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. ! Be sure that power is removed or the area is nonhazardous before proceeding. 3. Press on the module lock on the top of the module. 4. Pull on the I/O module to remove from the base. When you insert or remove the module while WARNING backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous ! before proceeding. 5. Repeat steps 1, 2, 3 and 4 for the module to the right. 6. Use a small bladed screwdriver to rotate the orange base locking screw to a vertical position. This releases the locking mechanism. 7. Then lift straight up to remove. Publication 1734-IN587B-EN-P - March 2002 POINT I/O 2 Relay Output Module 9 Communicating with Your Module I/O messages are sent to (consumed) and received from (produced) the POINT I/O modules. These messages are mapped into the processor’s memory. This POINT I/O output module does not produce input data (scanner Rx). It does consume 1 byte of I/O data (scanner Tx). Default Data Map for the 1734-OX2 Relay Output Module Message size: 1 Byte 76 543 2 1 0 Consumes Not used Ch Ch Channel state (scanner Tx) 1 0 Where: 0 = NO contact Off, NC contact On 1 = NO contact On, NC contact Off Publication 1734-IN587B-EN-P - March 2002 10 POINT I/O 2 Relay Output Module Wiring the Relay Output Module 01 Module Module Status Status Network Network Status 2 3 Status NODE: 4 5 Relay Output 0 6 Status of Output 0 7 1 Status of Output 1 1734 OX2 Output 0 Connection - NC NC - Output 1 Connection Output 0 Connection - NO NO - Output 1 Connection Output 0 Relay Common - RC RC - Output 1 Relay Common +V +V NC = Normally closed 41974 NO = Normally open RC = Relay Common +V = Positive Supply Relay contacts are not powered by the internal ATTENTION power bus. Load power can be provided by the internal power bus or an external power source. ! Publication 1734-IN587B-EN-P - March 2002 POINT I/O 2 Relay Output Module 11 Load powered by Internal Power Bus 0 1 Out 0 Out 1 NC NC 2 3 Out 0 Out 1 NO NO Load 4 5 Out 0 Out 1 L2/N L2/N Load RC RC L1 6 7 L1 +V +V NC = Normally closed NO = Normally open RC = Relay Common 42019OX +V = Positive Supply Channel Output Relay Common Supply 0 (N.C.) 0 46 0 (N.O.) 2 1 (N.C.) 1 57 1 (N.O.) 3 Supply voltage can range from +5V dc to 240V ac, depending on relay load. 12V, 24V dc, 120V, 240V ac power for the module is provided by the internal power bus. Publication 1734-IN587B-EN-P - March 2002 12 POINT I/O 2 Relay Output Module Load powered by External Power Bus L1 0 1 Power Out 0 Supply Out 1 NC NC Power 2 3 L1 Supply L2/N Out 0 Out 1 NO NO L2/N 4 5 Out 0 Out 1 Load Load RC RC 6 7 +V +V Out = Output channel relay contacts Power Supply = can range from +5V dc to 240V ac 42014OX RC = Relay Common 1 Channel Output Relay Common Supply 0 (N.C.) 0 46 0 (N.O.) 2 1 (N.C.) 1 57 1 (N.O.) 3 1 Supply voltage can range from +5V dc to 240V ac, depending on relay load. 12V, 24V dc, 120V, 240V ac power for the module is provided by the internal power bus Publication 1734-IN587B-EN-P - March 2002 POINT I/O 2 Relay Output Module 13 ATTENTION • Do not attempt to increase load current or wattage capability beyond the maximum rating by connecting 2 or more outputs in parallel. The slightest variation in relay switching time may cause one relay to momentarily switch the total load current. ! • Make certain that all relay wiring is properly connected before applying any power to the module. • Total current draw through the wiring base unit is limited to 10A. Separate power connections to the terminal base unit may be necessary. • Use the end cap from your adapter or interface module to cover the exposed interconnections on the last mounting base on the DIN rail. Failure to do so could result in equipment damage or injury from electric shock. PDN IB2 IV2 IB4 IV4 PDN OX2 OX2 FPD OX2 OX2 OX2 01 01 01 00 1 1 01 01 01 0 1 01 01 ac power bus CV L2/N L1 120V ac 24V dc Wiring with ac Wiring Using a 1734-FPD to 42090OX Modules only Create a New ac Power Bus Publication 1734-IN587B-EN-P - March 2002 14 POINT I/O 2 Relay Output Module IB2 IB4 IV2 IV4 OX2 OX2 OX2 PDN 01 01 01 01 01 01 01 01 24V L2/N L1 120V/240V ac 42010lt Wiring using external power source for ac Relay power Publication 1734-IN587B-EN-P - March 2002 POINT I/O 2 Relay Output Module 15 Troubleshooting with the Indicators Module Module Status Status Network Network Status Status NODE: Relay Output Status of Output 0 0 1 Status of Output 1 1734 OX2 Output 0 NC Connection Output 1 NC Connection Output 0 NO Connection Output 1 NO Connection Output 0 Relay Common Output 1 Relay Common +V +V 41974 Module Status Off No power applied to device Green Device operating normally Flashing Green Device needs commissioning due to configuration missing, incomplete or incorrect. Flashing Red Recoverable fault. Red Unrecoverable fault may require device replacement Flashing Red/Green Device is in self-test Publication 1734-IN587B-EN-P - March 2002 16 POINT I/O 2 Relay Output Module Indicator Indication Probable Cause Network Status Off Device is not on-line - Device has not completed dup_MAC_id test. - Device not powered - check module status indicator Flashing Green Device is on-line but has no connections in the established state. Green Device on-line and has connections in the established state. Flashing Red One or more I/O connections in timed-out state Red Critical link failure - failed communication device. Device detected error that prevents it communicating on the network. Flashing Communication faulted device - the device Red/Green has detected a network access error and is in communication faulted state. Device has received and accepted an Identify Communication Faulted Request - long protocol message. Indicator Indication Probable Cause I/O Status Off Output is off. Yellow Output is on. Publication 1734-IN587B-EN-P - March 2002 POINT I/O 2 Relay Output Module 17 Safety Approvals The following information applies when Informations sur l’utilisation de cet équipement operating this equipment in hazardous en environnements dangereux: locations: Products marked “CL I, DIV 2, GP A, B, C, D” are suitable Les produits marqués “CL I, DIV 2, GP A, B, C, D” ne for use in Class I Division 2 Groups A, B, C, D, Hazardous conviennent qu’à une utilisation en environnements de Classe Locations and nonhazardous locations only. Each product I Division 2 Groupes A, B, C, D dangereux et non dangereux. is supplied with markings on the rating nameplate Chaque produit est livré avec des marquages sur sa plaque indicating the hazardous location temperature code. When d’identification qui indiquent le code de température pour les combining products within a system, the most adverse environnements dangereux. Lorsque plusieurs produits sont temperature code (lowest “T” number) may be used to combinés dans un système, le code de température le plus help determine the overall temperature code of the défavorable (code de température le plus faible) peut être system. Combinations of equipment in your system are utilisé pour déterminer le code de température global du subject to investigation by the local Authority Having système. Les combinaisons d’équipements dans le système Jurisdiction at the time of installation. sont sujettes à inspection par les autorités locales qualifiées au moment de l’installation. EXPLOSION HAZARD - RISQUE D’EXPLOSION – WARNING • Do not disconnect equipment unless WARNING • Couper le courant ou s’assurer que power has been removed or the area l’environnement est classé non is known to be nonhazardous. dangereux avant de débrancher • Do not disconnect connections to l'équipement. this equipment unless power has • Couper le courant ou s'assurer que been removed or the area is known l’environnement est classé non ! ! to be nonhazardous. Secure any dangereux avant de débrancher les external connections that mate to connecteurs. Fixer tous les connecteurs this equipment by using screws, externes reliés à cet équipement à l'aide sliding latches, threaded de vis, loquets coulissants, connecteurs connectors, or other means provided filetés ou autres moyens fournis avec ce with this product. produit. • Substitution of components may • La substitution de composants peut impair suitability for Class I, Division rendre cet équipement inadapté à une 2. utilisation en environnement de Classe • If this product contains batteries, 1, Division 2. they must only be changed in an • S’assurer que l’environnement est area known to be nonhazardous. classé non dangereux avant de changer les piles. Publication 1734-IN587B-EN-P - March 2002 18 POINT I/O 2 Relay Output Module Specifications Specifications - 1734-OX2 Output Relay Module Outputs per Module 2 Form C isolated (normally open; normally closed) electromechanical relays Off-State Leakage 2.0mA and bleed resistor thru snubber circuit Current (max at 240V ac) Output Voltage Range (load 5-28.8V dc @ 2.0A resistive dependent) 48V dc @ 0.5A resistive 125V dc @ 0.25A resistive 125V ac @ 2.0A resistive 240V ac @ 2.0A resistive Output Current Rating Resistive (at rated power) 2A @ 5-28.8V dc 0.5A @ 48V dc 0.25A @ 125V dc 2A @ 125V ac 2A @ 240V ac Inductive 2.0A steady state @ 5-28.8V dc, L/R = 7ms 0.5A steady state @ 48V dc, L/R = 7ms 0.25A steady state @ 125V dc, L/R = 7ms 2.0A steady state, 15A make @ 125V ac, PF = cos θ = 0.4 2.0A steady state, 15A make @ 240V ac, PF = cos θ = 0.4 Power Rating 250W max. for 125V ac resistive output (steady state) 480W max. for 240V ac resistive output 60W max. for 28.8V dc resistive output 24W max. for 48V dc resistive output 31W max. for 125V dc resistive output 250VA max. for 125V ac inductive output 480VA max. for 240V ac inductive output 60VA max. for 28.8V dc inductive output 24VA max. for 48V dc inductive output 31VA max. for 125V dc inductive output Output Signal Delay OFF to ON 10ms maximum (time from valid output on signal to relay energization by module) ON to OFF 10ms maximum (time from valid output off signal to relay deenergization by module) Initial Contact Resistance 30mΩ Switching Frequency 1 operation/3s (0.3Hz at rated load) max Operate/Release Time 10ms max Bounce Time 1.2ms (mean) Minimum Contact Load 5mA per point Expected Life of Minimum 1,000,000 cycles resistive Electrical Contacts 100,000 cycles inductive Publication 1734-IN587B-EN-P - March 2002 POINT I/O 2 Relay Output Module 19 Fusing Module outputs are not fused. If fusing is desired, you must supply external fusing. Indicators 2 green/red module/network status 2 yellow output status Keyswitch position 7 General Specifications Module Location 1734-TB or -TBS wiring base assembly Pointbus Current 100mA max @ 5V dc Power Dissipation 0.5W max Thermal Dissipation 1.7 BTU/hr max Isolation Voltage Between any 2 sets 250V continuous (Tested to 2550V dc for 1s) of contacts Customer load to logic 250V continuous (Tested to 2550V dc for 1s) Field Power Bus Supply Voltage None required Voltage Range 240V ac max Supply Current 2A per channel maximum, 4A per module Dimensions Inches 2.21H x 0.47W x 2.97L (Millimeters) (56H x 12W x 75.5L) Environmental Conditions Operational Temperature IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20 to 55°C (-4 to 131°F) Storage Temperature IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): -40 to 85°C (-40 to 185°F) Relative Humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat): 5 to 95% noncondensing Shock IEC60068-2-27 (Test Ea, Unpackaged Shock) Operating 30g peak acceleration Non-operating 50g peak acceleration Vibration IEC60068-2-6, (Test Fc, Operating) Tested 5g @ 10-500Hz ESD Immunity IEC 61000-4-2: 6kV contact discharges 8kV air discharges Radiated RF Immunity IEC 61000-4-3: 10V/m with 1kHz sine-wave 80%AM from 80MHz to 1000MHz 10V/m with 200Hz 50% Pulse 100%AM at 900Mhz Publication 1734-IN587B-EN-P - March 2002 EFT/B Immunity IEC 61000-4-4: ±2kV at 5kHz on signal ports Surge Transient Immunity IEC 61000-4-5: ±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports Conducted RF Immunity IEC 61000-4-6: 10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz Emissions CISPR 11; Group 1, Class A Enclosure Type Rating None (open-style) 2 2 Conductors Wire Size 14 AWG (2.5mm ) - 22 AWG (0.25mm ) solid or stranded copper wire rated @ 75°C or greater 3/64 inch (1.2mm) insulation maximum Category 1 2 Terminal Base Screw Torque 7 pound-inches (0.6Nm) Field Wiring Terminations 0 - Output 0 - NC 1 - Output 1 - NC 2 - Output 0 - NO 3 - Output 1 - NO 4 - Relay Common 0 5 - Relay Common 1 6 - +Supply 7 - +Supply Mass 1.30 oz/36.9 grams Agency Certification (when product UL - UL Listed Industrial Control Equipment, certified C- -US is marked) for US and Canada UL - UL Listed for Class I, Division 2, Groups A, B, C C- -US and D Hazardous locations, certified for US and Canada 2 CE - European Union 89/336/EEC EMC Directive, compliant with: EN 50081-2; Industrial Emissions EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity 2 C-Tick - Australian Radiocommunications Act compliant with AS/NZS 2064, Industrial Emissions ODVA - ODVA Conformance tested to ODVA DeviceNet specifications 1 Use this conductor category information for planning conductor routing. Refer to publication 1770-4.1, “Industrial Automation Wiring and Grounding Guidelines.” 2 See the Product Certification link at www.ab.com for Declaration of Conformity, Certificates, and other certification details. Publication 1734-IN587B-EN-P - March 2002 PN 957657-97 Supersedes 1734-IN587A-EN-P - December 2001 © 2002 Rockwell International Corporation. Printed in USA

Frequently asked questions

How does Industrial Trading differ from its competitors?

chervon down
Industrial Trading' parent company, GID Industrial, specializes in procuring industrial parts. We know where to find the rare and obsolete equipment that our customers need in order to get back to business. There are other companies who claim to do what we do, but we're confident that our commitment to quality and value is unparalleled in our field.

Is there a warranty for the 1734-OX2?

chervon down
The warranty we offer will be based on what we negotiate with our suppliers. Sometimes, a part will be sold as-is and without a warranty. Our specialty, single board computers, tend to receive a one-year warranty.

Which carrier will Industrial Trading use to ship my parts?

chervon down
We use FedEx, UPS, DHL, and USPS. We have accounts with each of them and generally ship using one of those, but we can also ship using your account if you would prefer. However, we can use other carriers if it will be more convenient for you.

Can I buy parts from Industrial Trading if I am outside the USA?

chervon down
Industrial Trading will definitely serve you. We work with international clients all the time, and we are familiar with shipping to destinations all across the globe.

Which payment methods does Industrial Trading accept?

chervon down
Visa, MasterCard, Discover, and American Express are all accepted by Industrial Trading. We will also accept payment made with wire transfer or PayPal. Checks will only be accepted from customers in the USA. Terms may available for larger orders, upon approval.

Why buy from GID?

quality

Quality

We are industry veterans who take pride in our work

protection

Protection

Avoid the dangers of risky trading in the gray market

access

Access

Our network of suppliers is ready and at your disposal

savings

Savings

Maintain legacy systems to prevent costly downtime

speed

Speed

Time is of the essence, and we are respectful of yours

What they say about us

FANTASTIC RESOURCE

star star star star star

One of our top priorities is maintaining our business with precision, and we are constantly looking for affiliates that can help us achieve our goal. With the aid of GID Industrial, our obsolete product management has never been more efficient. They have been a great resource to our company, and have quickly become a go-to supplier on our list!

Bucher Emhart Glass

EXCELLENT SERVICE

star star star star star

With our strict fundamentals and high expectations, we were surprised when we came across GID Industrial and their competitive pricing. When we approached them with our issue, they were incredibly confident in being able to provide us with a seamless solution at the best price for us. GID Industrial quickly understood our needs and provided us with excellent service, as well as fully tested product to ensure what we received would be the right fit for our company.

Fuji

HARD TO FIND A BETTER PROVIDER

star star star star star

Our company provides services to aid in the manufacture of technological products, such as semiconductors and flat panel displays, and often searching for distributors of obsolete product we require can waste time and money. Finding GID Industrial proved to be a great asset to our company, with cost effective solutions and superior knowledge on all of their materials, it’d be hard to find a better provider of obsolete or hard to find products.

Applied Materials

CONSISTENTLY DELIVERS QUALITY SOLUTIONS

star star star star star

Over the years, the equipment used in our company becomes discontinued, but they’re still of great use to us and our customers. Once these products are no longer available through the manufacturer, finding a reliable, quick supplier is a necessity, and luckily for us, GID Industrial has provided the most trustworthy, quality solutions to our obsolete component needs.

Nidec Vamco

TERRIFIC RESOURCE

star star star star star

This company has been a terrific help to us (I work for Trican Well Service) in sourcing the Micron Ram Memory we needed for our Siemens computers. Great service! And great pricing! I know when the product is shipping and when it will arrive, all the way through the ordering process.

Trican Well Service

GO TO SOURCE

star star star star star

When I can't find an obsolete part, I first call GID and they'll come up with my parts every time. Great customer service and follow up as well. Scott emails me from time to time to touch base and see if we're having trouble finding something.....which is often with our 25 yr old equipment.

ConAgra Foods

Related Products

product

Rockwell Automation 1734-232ASC Serial I/O Modules- Inputs/Outputs 1 Serial Interface channel, Point...

product

Rockwell Automation 1734-485ASC Serial I/O Modules- Inputs/Outputs 1 Serial Interface channel, Point...

product

Allen Bradley 1734-ADN I/O Adapter Module - 24V DC DeviceNet Adapter

product

Allen Bradley 1734-ADNX Adapter Module - DeviceNet I/O Adapter with Expansion Port, 63 POINT I/O mod...

product

Allen Bradley 1734d-IA16 PointBlock I/O Module - 120 VAC, 16 Inputs, DNET communication interface

product

Allen Bradley 1734d-IA16S PointBlock I/O Module - 120 VAC, 16 Inputs, DNET communication interface, ...