ALLEN-BRADLEY 1734-IB2

Description

Allen Bradley 1734-IB2 POINt I/O Input Module - 24V DC 2 channel sinking input module

Part Number

1734-IB2

Price

Request Quote

Manufacturer

ALLEN-BRADLEY

Lead Time

Request Quote

Category

I/O Module

Specifications

Certifications

CE, C-Tick, DeviceNet, ATEX, TÃœV-certified for functional safety up to and including SIL 3, Cat. 4, PL(e)

Conducted RF Immunity

10Vrms with 1 kHz sine-wave 80%AM from 150 kHz to 80MHz

Conductors

Wire Size:14 AWG (2.5 mm2) - 22 AWG (0.25 mm2) solid or stranded copper wire rated at 75 °C or greater, 3/64 inch (1.2mm) insulation maximum, Category2:1

Dimensions

Metric:(56H x 12W x 75.5L mm), Imperial:2.2H x 0.47W x 2.97L in.

EFT/B Immunity

±4 kV at 5 kHz on signal ports

Emissions

CISPR 11:Group 1, Class A

Enclosure Type Rating

None (open-style)

ESD Immunity

6 kV contact discharges, 8 kV air discharges

Field Power Bus Supply Voltage Voltage Range

24V dc nominal, 10-28.8V dc

Field Wiring Terminations

0 - Input 01 - Input 1, 2 - No Connection3 - No Connection

Indicators

1 green/red network status indicator, logic side, 1 green/red module status indicator, logic side, 2 yellow input status indicators, logic side

Input Filter Time1

OFF to ON:0.5 ms hardware plus 0-63 ms (user selectable), ON to OFF:0.5 ms hardware plus 0-63 ms (user selectable)

Input Impedance

4.7 KO maximum, 3.6 KO nominal

Inputs per Module

2 (1 group of 2), sinking

Isolation Voltage (continuous voltage withstanding rating)

50V, Tested to withstand 2500V dc for 60 s

Keyswitch Position

1

Mass

1.09 oz/30.9 grams

Module Location

1734-TB or 1734-TBS wiring base assembly

Nonoperating Shock

50 g

Nonoperating Temperature

-40…85 °C (-40…185 °F)

OFF-State Current

1.5 mA minimum

OFF-State Voltage

5V dc maximum

ON-State Current

2 mA minimum, 4 mA nominal @ 24V dc, 5 mA maximum

ON-State Voltage

10V dc minimum, 24V dc nominal, 28.8V dc maximum

Operating Shock

30 g

Operational Temperature

-20 to 55 °C (-4 to 131 °F)

POINT I/O Input Modules

21

Pointbus Current

75 mA maximum @ 5V dc

Power Dissipation

0.7 W maximum @ 28.8V dc

Radiated RF Immunity

10V/m with 200 Hz 50% Pulse 100%AM at 900 Mhz, 10V/m with 1 kHz sine-wave 80%AM from 30 MHz to 2000 MHz, 10V/m with 200 Hz 50% Pulse 100%AM at 1890 Mhz

Relative Humidity

5…95% noncondensing

Storage Temperature

-40 to 85 °C (-40 to 185 °F)

Surge Transient Immunity

±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports

Terminal Base Screw Torque

7 pound-inches (0.8 Nm)

Thermal Dissipation

2.4 BTU/hr maximum @ 28.8V dc

Vibration

5 g at 10…500 Hz

Datasheet

pdf file

Allen Bradley=1734-IB2_IB4_IB8=datashee-656286441t.pdf

597 KiB

Extracted Text

Installation Instructions POINT I/O Input Modules Cat. No. 1734-IB2, 1734-IB4, 1734-IB8, Series C Inside… For See Page Important User Information 2 Before You Begin 4 Identify the Components 5 About the Module 5 Install the Mounting Base 5 Install the I/O Module 6 Install the Removable Terminal Block (RTB) 7 Remove a Mounting Base 7 Communicate with Your Module 9 Wire the Input Modules 10 Wiring for 1734-IB2 11 Wiring for 1734-IB4 12 Wiring for 1734-IB8 13 Troubleshoot with the Indicators 16 Safety Approvals 18 Specifications for 1734-IB2, 1734-IB4, and 20 1734-IB8 Input Modules Publication 1734-IN051F-EN-E - August 2005 2 POINT I/O Input Modules Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.literature.rockwellautomation.com) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual we use notes to make you aware of safety considerations. Identifies information about practices or circumstances that can cause an WARNING explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. Identifies information about practices or circumstances that can lead to personal ATTENTION injury or death, property damage, or economic loss. Attentions help you: • identify a hazard • avoid a hazard • recognize the consequence Labels may be located on or inside the equipment (e.g., drive or motor) to alert SHOCK HAZARD people that dangerous voltage may be present. Labels may be located on or inside the equipment (e.g., drive or motor) to alert BURN HAZARD people that surfaces may be dangerous temperatures. Identifies information that is critical for successful application and understanding IMPORTANT of the product. Publication 1734-IN051F-EN-E - August 2005 POINT I/O Input Modules 3 Environment and Enclosure ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as "open type" equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, see the appropriate sections in this publication, as well as the Allen-Bradley publication 1770-4.1 (Industrial Automation Wiring and Grounding Guidelines), for additional installation requirements pertaining to this equipment. POINT I/O is grounded through the DIN rail to chassis ATTENTION ground. Use zinc plated, yellow chromated steel DIN rail to assure proper grounding. Using other DIN rail materials (e.g. aluminum, plastic, etc.) which can corrode, oxidize or are poor conductors can result in improper or intermittent platform grounding. Publication 1734-IN051F-EN-E - August 2005 4 POINT I/O Input Modules EXPLOSION HAZARD WARNING • Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous. • Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product. • Substitution of components may impair suitability for Class I, Division 2. • If this product contains batteries, they must only be changed in an area known to be nonhazardous. Preventing Electrostatic Discharge ATTENTION This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • Touch a grounded object to discharge potential static. • Wear an approved grounding wriststrap. • Do not touch connectors or pins on component boards. • Do not touch circuit components inside the equipment. • If available, use a static-safe workstation. • When not in use, store the equipment in appropriate static-safe packaging. Before You Begin This Series C POINT I/O product can be used with DeviceNet and PROFIBUS adapters. It can be used with ControlNet and Ethernet adapters using RSLogix 5000 software, version 11 or higher. Read this manual for information about how to install this 1734 POINT I/O Module. Publication 1734-IN051F-EN-E - August 2005 POINT I/O Input Modules 5 Identify the Components Use the figure to identify the external features of the module. Slide-in Writable Label Mechanical Locking Insertable I/O Mechanism Module Wiring Mechanical Diagram RTB Removal Keying DIN Rail Handle Licking Screw Removal Terminal Block (RTB) Interlocking Side Pieces Mounting Base About the Module The 1734 sink input modules are available in 2 input, 4 input, and 8 input. They install in mounting bases that mount on a DIN rail. All wiring is made to a removable terminal block mounted on the mounting base. Install the Mounting Base To install the mounting base on the DIN rail, proceed as follows. 1. Position the mounting base vertically above the installed units (adapter, power supply, or existing module). Publication 1734-IN051F-EN-E - August 2005 Module Status Network Status NODE: 0 1 2 3 6 POINT I/O Input Modules 2. Slide the mounting base down allowing the interlocking side pieces to engage the adjacent module or adapter. 3. Press firmly to seat the mounting base on the DIN rail. The mounting base will snap into place. 4. To remove the mounting base from the DIN rail, remove the module, and use a small bladed screwdriver to rotate the base locking screw to a vertical position. This releases the locking mechanism. 5. Lift straight up to remove. Install the I/O Module The module can be installed before, or after base installation. Make sure that the mounting base is correctly keyed before installing the module into the mounting base. In addition, make sure the mounting base locking screw is positioned horizontal referenced to the base. When you insert or remove the module while WARNING backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation. 1. Using a bladed screwdriver, rotate the keyswitch (2) on the mounting base clockwise until the number required for the type of module being installed aligns with the notch in the base. 2. Make certain the DIN rail locking screw is in the horizontal position. You cannot insert the module if the locking mechanism is unlocked. Publication 1734-IN051F-EN-E - August 2005 POINT I/O Input Modules 7 3. Insert the module straight down into the mounting base and press to secure. The module will lock into place. Install the Removable Terminal Block (RTB) A removable terminal block is supplied with your wiring base assembly. To remove, pull up on the RTB handle. This allows the mounting base to be removed and replaced as necessary without removing any of the wiring. To reinsert the removable terminal block, proceed as follows. 1. Insert the end opposite the handle into the base unit. This end has a curved section that engages with the wiring base. 2. Rotate the terminal block into the wiring base until it locks itself in place. 3. If an I/O module is installed, snap the RTB handle into place on the module. When you connect or disconnect the removable terminal WARNING block (RTB) with field side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Remove a Mounting Base To remove a mounting base, you must remove any installed module, and the module installed in the base to the right. Remove the removable terminal block (if wired). 1. Unlatch the RTB handle on the I/O module. Publication 1734-IN051F-EN-E - August 2005 8 POINT I/O Input Modules 2. Pull on the RTB handle to remove the removable terminal block. When you connect or disconnect the removable terminal WARNING block (RTB) with field side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. 3. Press on the module lock on the top of the module. 4. Pull on the I/O module to remove from the base. When you insert or remove the module while backplane WARNING power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation. 5. Repeat steps 1, 2, 3, and 4 for the module to the right. 6. Use a small bladed screwdriver to rotate the orange base locking screw to a vertical position. This releases the locking mechanism. 7. Lift straight up to remove. Publication 1734-IN051F-EN-E - August 2005 POINT I/O Input Modules 9 Communicate with Your Module I/O messages are sent to (consumed) and received from (produced) the POINT I/O modules. These messages are mapped into the processor’s memory. This POINT I/O input module produces 1 byte of input data (scanner Rx). It does not consume I/O data (scanner Tx). Default Data Map for the 1734-IB2 Input Module Message size: 1 Byte 7 6 5 4 3 2 1 0 Produces (Rx) I1 I0 Consumes (Tx) No consumed data Where: I0 = channel 0, I1 = channel 1; 0 = off, 1 = on Default Data Map for the 1734-IB4 Input Module Message size: 1 Byte 7 6 5 4 3 2 1 0 Produces (Rx) I3 I2 I1 I0 Consumes (Tx) No consumed data Where: I0 = channel 0, I1 = channel 1, I2 = channel 2 and I3 = channel 3; 0 = off, 1 = on Default Data Map for the 1734-IB8 Input Module Message size: 1 Byte 7 6 5 4 3 2 1 0 Produces (Rx) I7 I6 I5 I4 I3 I2 I1 I0 Consumes (Tx) No consumed data Where: I0 = channel 0, I1 = channel 1, I2 = channel 2 and I3 = channel 3; I4 = channel 4, I5 = channel 5, I6 = channel 6, I7 equals channel 7; 0 = off, 1 = on Publication 1734-IN051F-EN-E - August 2005 10 POINT I/O Input Modules Wire the Input Modules 1734-IB2 1734-IB4 1734-IB8 Module Status Module Module Module Status Status Status Network Status Network Network Network Status Status Status NODE: NODE: NODE: 24VDC 24VDC 24VDC Sink Sink Sink Input Input Input Status of Input 0 Status - Input 0 & 4 0 0 0 4 Status of Input 1 Status - Input 1 & 5 1 1 1 5 Status of Input 2 Status - Input 2 & 6 2 2 6 Status - Input 3 & 7 Status of Input 3 3 3 7 1734 1734 1734 IB2 IB4 IB8 Input 1 Input 0 Input 0 Input 1 nput 0 Input 1 Input 2 Input 3 Input 2 Input 3 NC NC C C C C Input 4 Input 5 V V V V Input 6 Input 7 Input = 0 and 1 Input = 0, 1, 2, 3, 4, 5, 6 and 7 Input = 0, 1, 2 and 3 NC = No Connection (2 and 3) Note: V and C are daisychained C = Common (4 and 5) C = Common (4 and 5) from either the adapter, 1734-FPD, 1734-EP24DC, or from a user-supplied auxiliary terminal block. 41974 When you connect or disconnect wiring while field side WARNING power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Publication 1734-IN051F-EN-E - August 2005 POINT I/O Input Modules 11 Wiring for 1734-IB2 When you connect or disconnect wiring while field side WARNING power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Sink Input 01 In 0 In 1 2 3 Prox Prox NC NC 4 5 2-wire 3-wire C C 6 7 VV V = 12/24V dc 41966 C = Common Channel Input Common Voltage 0 0 4 6 1 1 5 7 Connect common on 3-wire proximity switches. 12/24V dc is supplied through the internal power bus. Publication 1734-IN051F-EN-E - August 2005 12 POINT I/O Input Modules Wiring for 1734-IB4 When you connect or disconnect wiring while field side WARNING power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Sink Input 01 In 0 In 1 2-wire 3-wire 2 3 In 2 In 3 Prox Prox Prox Prox 4 5 C C 6 7 VV 41967 V = 12/24V dc C = Common Channel Input Common Voltage 0 0 4 6 1 1 5 7 2 2 4 6 3 3 5 7 Connect common on 3-wire proximity switches. 12/24V dc is supplied through the internal power bus. Publication 1734-IN051F-EN-E - August 2005 POINT I/O Input Modules 13 Wiring for 1734-IB8 When you connect or disconnect wiring while field side WARNING power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Sink Input 3-wire 3-wire 01 Prox Prox In 0 In 1 2-wire 2-wire 2 3 Prox Prox In 2 In 3 3-wire 3-wire 4 5 Prox Prox In 4 In 5 2-wire 2-wire 6 7 Prox In 6 Prox In 7 V C C V V = 12/24V dc 41967 C = Common Channel Input Channel Input 0 0 4 4 1 1 5 5 2 2 6 6 3 3 7 7 Daisychain common and power connections from 1734 adapter, 1734-FPD, 1734-EP24DC, or from user-supplied external auxiliary terminal block. Note: When connecting more than 1 wire in a termination point, make sure that both wires are the same gauge and type. Publication 1734-IN051F-EN-E - August 2005 14 POINT I/O Input Modules Example of Wiring for 1734-IB8 Using 2-Wire Proximity Switches When you connect or disconnect wiring while field side WARNING power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Module Module Status Status Network Network Status Status DeviceNet 0 4 0 4 1 5 1 5 2 6 2 6 System Power 3 7 3 7 DeviceNet Power 1734 1734 IB8 OB8E Prox Prox Prox Prox Prox Prox Prox Prox 24V dc Return 24V dc Terminal Block with Bus connector strip Publication 1734-IN051F-EN-E - August 2005 POINT I/O Input Modules 15 Example of Wiring for 1734-IB8 Using 3-Wire Proximity Switches When you connect or disconnect wiring while field side WARNING power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Module Module Status Status Network Network Status Status DeviceNet 0 4 0 4 1 5 1 5 2 6 2 6 System Power 3 7 3 7 DeviceNet Power 1734 1734 OB8E IB8 Prox Prox Prox Prox Prox Prox Prox Prox 24V dc Return 24V dc Terminal Block with bus connector strip Terminal Block with bus connector strip Publication 1734-IN051F-EN-E - August 2005 16 POINT I/O Input Modules Troubleshoot with the Indicators 1734-IB2 1734-IB4 1734-IB8 Module Module Status Module Module Module Status Status Status Status Network Network Status Network Network Status Network Status Status Status NODE: NODE: NODE: 24VDC 24VDC 24VDC Sink Sink Sink Input Input Input Status of Input 0 0 Status of Input 0 & 4 0 0 4 1 Status of Input 1 Status of Input 1 & 5 1 5 1 Status of Input 2 2 6 2 Status of Input 2 & 6 Status of Input 3 3 7 3 Status of Input 3 & 7 1734 1734 1734 IB2 IB8 IB4 Indication Probable Cause Module Status Off No power applied to device Green Device operating normally Flashing Green Device needs commissioning due to configuration missing, incomplete or incorrect. Flashing Red Recoverable fault. Red Unrecoverable fault may require device replacement Flashing Red/Green Device is in self-test Publication 1734-IN051F-EN-E - August 2005 POINT I/O Input Modules 17 Indication Probable Cause Network Status Off Device is not on line - Device has not completed dup_MAC_id test. - Device not powered - check module status indicator Flashing Green Device is on line but has no connections in the established state. Green Device on-line and has connections in the established state. Flashing Red One or more I/O connections in timed-out state Red Critical link failure - failed communication device. Device detected error that prevents it communicating on the network. Flashing Red/Green Communication faulted device - the device has detected a network access error and is in communication faulted state. Device has received and accepted an Identify Communication Faulted Request - long protocol message. Indication Probable Cause I/O Status Off Input is in the off state Yellow Input is in the on state Publication 1734-IN051F-EN-E - August 2005 18 POINT I/O Input Modules Safety Approvals North American Hazardous Location Approval The following information applies when Informations sur l’utilisation de cet équipement operating this equipment in hazardous en environnements dangereux: locations: Products marked “CL I, DIV 2, GP A, B, C, D” are suitable Les produits marqués “CL I, DIV 2, GP A, B, C, D” ne for use in Class I Division 2 Groups A, B, C, D, Hazardous conviennent qu’à une utilisation en environnements de Classe I Locations and nonhazardous locations only. Each product Division 2 Groupes A, B, C, D dangereux et non dangereux. is supplied with markings on the rating nameplate Chaque produit est livré avec des marquages sur sa plaque indicating the hazardous location temperature code. When d’identification qui indiquent le code de température pour les combining products within a system, the most adverse environnements dangereux. Lorsque plusieurs produits sont temperature code (lowest “T” number) may be used to combinés dans un système, le code de température le plus help determine the overall temperature code of the défavorable (code de température le plus faible) peut être system. Combinations of equipment in your system are utilisé pour déterminer le code de température global du subject to investigation by the local Authority Having système. Les combinaisons d’équipements dans le système Jurisdiction at the time of installation. sont sujettes à inspection par les autorités locales qualifiées au moment de l’installation. EXPLOSION HAZARD - RISQUE D’EXPLOSION – WARNING AVERTISSEMENT • Do not disconnect equipment unless • Couper le courant ou s’assurer que power has been removed or the area l’environnement est classé non is known to be nonhazardous. dangereux avant de débrancher l'équipement. • Do not disconnect connections to this equipment unless power has • Couper le courant ou s'assurer que been removed or the area is known l’environnement est classé non to be nonhazardous. Secure any dangereux avant de débrancher les external connections that mate to connecteurs. Fixer tous les this equipment by using screws, connecteurs externes reliés à cet sliding latches, threaded équipement à l'aide de vis, loquets connectors, or other means provided coulissants, connecteurs filetés ou with this product. autres moyens fournis avec ce produit. • Substitution of components may impair suitability for Class I, Division • La substitution de composants peut 2. rendre cet équipement inadapté à une utilisation en environnement de • If this product contains batteries, Classe 1, Division 2. they must only be changed in an area known to be nonhazardous. • S’assurer que l’environnement est classé non dangereux avant de changer les piles. Publication 1734-IN051F-EN-E - August 2005 POINT I/O Input Modules 19 European Hazardous Location Approval European Zone 2 Certification (The following applies when the product bears the EEx Marking) This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC. DEMKO certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres, given in Annex II to this Directive. The examination and test results are recorded in confidential report No. 03NK30347. Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 50021. Observe the following additional Zone 2 certification IMPORTANT requirements. • This equipment is not resistant to sunlight or other sources of UV radiation. • The secondary of a current transformer shall not be open-circuited when applied in Class I, Zone 2 environments. • Equipment of lesser Enclosure Type Rating must be installed in an enclosure providing at least IP54 protection when applied in Class I, Zone 2 environments. • This equipment shall be used within its specified ratings defined by Allen-Bradley. • Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40% when applied in Class I, Zone 2 environments Publication 1734-IN051F-EN-E - August 2005 20 POINT I/O Input Modules Specifications for 1734-IB2, 1734-IB4, and 1734-IB8 Input Modules General Specifications Specification Value (IEC 3 24V dc Input Compliant) Module Location 1734-TB or 1734-TBS wiring base assembly Inputs per Module 1734-IB2 - 2 (1 group of 2), sinking 1734-IB4 - 4 (1 group of 4), sinking 1734-IB8 - 8 (1 group of 8), sinking ON-State Voltage 10V dc minimum 24V dc nominal 28.8V dc maximum ON-State Current 2 mA minimum 4 mA nominal @ 24V dc 5 mA maximum OFF-State Voltage 5V dc maximum OFF-State Current 1.5 mA minimum Input Impedance 4.7 KΩ maximum, 3.6 KΩ nominal Pointbus Current 75 mA maximum @ 5V dc Power Dissipation 1734-IB2 - 0.7 W maximum @ 28.8V dc 1734-IB4 - 1.0 W maximum @ 28.8V dc 1734-IB8 - 1.6 W maximum @ 28.8V dc Thermal Dissipation 1734-IB2 - 2.4 BTU/hr maximum @ 28.8V dc 1734-IB4 - 3.4 BTU/hr maximum @ 28.8V dc 1734-IB8 - 5.5 BTU/hr maximum @ 28.8V dc Isolation Voltage 50V (continuous voltage Tested to withstand 2500V dc for 60 s withstanding rating) Field Power Bus Supply Voltage 24V dc nominal Voltage Range 10-28.8V dc 1 Input Filter Time 0.5 ms hardware plus 0-63 ms (user selectable) OFF to ON 0.5 ms hardware plus 0-63 ms (user selectable) ON to OFF Dimensions Metric) (56H x 12W x 75.5L mm) Imperial( 2.2H x 0.47W x 2.97L in. Terminal Base Screw 7 pound-inches (0.8 Nm) Torque Publication 1734-IN051F-EN-E - August 2005 POINT I/O Input Modules 21 Mass 1734-IB2 - 1.09 oz/30.9 grams 1734-IB4 - 1.12 oz/31.8 grams 1734-IB8 - 1.14 oz/32.3 grams Indicators 1 green/red network status indicator, logic side 1 green/red module status indicator, logic side 1734-IB2 - 2 yellow input status indicators, logic side 1734-IB4 - 4 yellow input status indicators, logic side 1734-IB8 - 8 yellow input status indicators, logic side Keyswitch Position 1 Field Wiring Terminations 1734-IB2 0 - Input 0 1 - Input 1 2 - No Connection 3 - No Connection 4 - Common 5 - Common 6 - User Supply 7 - User Supply 1734-IB4 0 - Input 0 1 - Input 1 2 - Input 2 3 - Input 3 4 - Common 5 - Common 6 - User Supply 7 - User Supply 1734-IB8 0 - Input 0 1 - Input 1 2 - Input 2 3 - Input 3 4 - Input 4 5 - Input 5 6 - Input 6 7 - Input 7 2 2 Conductors Wire Size 14 AWG (2.5 mm ) - 22 AWG (0.25 mm ) solid or stranded copper wire rated at 75 °C or greater 3/64 inch (1.2mm) insulation maximum 2 Category 1 1 Input off-to-on filter time is the time from a valid input signal to recognition by the module. Input on-to-off time is the time from a valid input signal to recognition by the module. 2 Use this conductor category information for planning conductor routing. Refer to publication 1770-4.1, “Industrial Automation Wiring and Grounding Guidelines.” Environmental Specifications Specification Value Operational Temperature IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20 to 55 °C (-4 to 131 °F) Storage Temperature IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): -40 to 85 °C (-40 to 185 °F) Publication 1734-IN051F-EN-E - August 2005 22 POINT I/O Input Modules Relative Humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat): 5 to 95% noncondensing Shock IEC 60068-2-27 (Test Ea, Unpackaged Shock) Operating 30g Non-operating 50g Vibration IEC 60068-2-6, (Test Fc, Operating) 5g @ 10-500 Hz ESD Immunity IEC 61000-4-2: 6 kV contact discharges 8 kV air discharges IEC 61000-4-3: Radiated RF Immunity 10V/m with 200 Hz 50% Pulse 100%AM at 900 Mhz 10V/m with 1 kHz sine-wave 80%AM from 30 MHz to 2000 MHz 10V/m with 200 Hz 50% Pulse 100%AM at 1890 Mhz IEC 61000-4-4: EFT/B Immunity ±4 kV at 5 kHz on signal ports IEC 61000-4-5: Surge Transient ±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports Immunity IEC 61000-4-6: Conducted RF Immunity 10Vrms with 1 kHz sine-wave 80%AM from 150 kHz to 80MHz Emissions CISPR 11: Group 1, Class A Enclosure Type Rating None (open-style) Publication 1734-IN051F-EN-E - August 2005 POINT I/O Input Modules 23 Certification Specifications Certification Value Certifications: (when C-UL-US - UL Listed Industrial Control Equipment, 1 certified for US and Canada product is marked) C-UL-US - UL Listed for Class I, Division 2, Groups A, B, C and D Hazardous locations, certified for US and Canada EEx European Union 94/9/EEC ATEX Directive, compliant with: EN 50021; Potentially Explosive Atmospheres, Protection “n” (Zone 2) CE - European Union 89/336/EEC EMC Directive, compliant with: EN 61000-6-4; Industrial Emissions EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity C-Tick - Australian Radiocommunications Act compliant with AS/NZS CISPR 11, Industrial Emissions 1 See the Product Certification link at www.ab.com for Declaration of Conformity, Certificates, and other certification details. POINT I/O, POINTBus, RSLogix5, RSLogix500, and RSLogix5000, are trademarks of Rockwell Automation. DeviceNet is a trademark of the Open DeviceNet Vendor Association. ControlNet is a trademark of ControlNet International, Ltd. PROFIBUS (Logo is registered, use restricted to members of PROFIBUS International only). EtherNet/IP is a trademark of ControlNet International, Ltd. under license by Open DeviceNet Vendor Association. . DeviceNet Publication 1734-IN051F-EN-E - August 2005 Rockwell Automation Support Rockwell Automation provides technical information on the web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com. Installation Assistance If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running: United States 1.440.646.3223 Monday – Friday, 8am – 5pm EST Outside United States Please contact your local Rockwell Automation representative for any technical support issues. New Product Satisfaction Return Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned: United States Contact your distributor. You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process. Outside United States Please contact your local Rockwell Automation representative for return procedure. Publication 1734-IN051F-EN-E - August 2005 PN 957974-15 Supersedes Publication 1734-IN051E-EN-E - February 2005 Copyright © 2005 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

Frequently asked questions

How does Industrial Trading differ from its competitors?

chervon down
Industrial Trading' parent company, GID Industrial, specializes in procuring industrial parts. We know where to find the rare and obsolete equipment that our customers need in order to get back to business. There are other companies who claim to do what we do, but we're confident that our commitment to quality and value is unparalleled in our field.

Is there a warranty for the 1734-IB2?

chervon down
The warranty we offer will be based on what we negotiate with our suppliers. Sometimes, a part will be sold as-is and without a warranty. Our specialty, single board computers, tend to receive a one-year warranty.

Which carrier will Industrial Trading use to ship my parts?

chervon down
We use FedEx, UPS, DHL, and USPS. We have accounts with each of them and generally ship using one of those, but we can also ship using your account if you would prefer. However, we can use other carriers if it will be more convenient for you.

Can I buy parts from Industrial Trading if I am outside the USA?

chervon down
Industrial Trading will definitely serve you. We work with international clients all the time, and we are familiar with shipping to destinations all across the globe.

Which payment methods does Industrial Trading accept?

chervon down
Visa, MasterCard, Discover, and American Express are all accepted by Industrial Trading. We will also accept payment made with wire transfer or PayPal. Checks will only be accepted from customers in the USA. Terms may available for larger orders, upon approval.

Why buy from GID?

quality

Quality

We are industry veterans who take pride in our work

protection

Protection

Avoid the dangers of risky trading in the gray market

access

Access

Our network of suppliers is ready and at your disposal

savings

Savings

Maintain legacy systems to prevent costly downtime

speed

Speed

Time is of the essence, and we are respectful of yours

What they say about us

FANTASTIC RESOURCE

star star star star star

One of our top priorities is maintaining our business with precision, and we are constantly looking for affiliates that can help us achieve our goal. With the aid of GID Industrial, our obsolete product management has never been more efficient. They have been a great resource to our company, and have quickly become a go-to supplier on our list!

Bucher Emhart Glass

EXCELLENT SERVICE

star star star star star

With our strict fundamentals and high expectations, we were surprised when we came across GID Industrial and their competitive pricing. When we approached them with our issue, they were incredibly confident in being able to provide us with a seamless solution at the best price for us. GID Industrial quickly understood our needs and provided us with excellent service, as well as fully tested product to ensure what we received would be the right fit for our company.

Fuji

HARD TO FIND A BETTER PROVIDER

star star star star star

Our company provides services to aid in the manufacture of technological products, such as semiconductors and flat panel displays, and often searching for distributors of obsolete product we require can waste time and money. Finding GID Industrial proved to be a great asset to our company, with cost effective solutions and superior knowledge on all of their materials, it’d be hard to find a better provider of obsolete or hard to find products.

Applied Materials

CONSISTENTLY DELIVERS QUALITY SOLUTIONS

star star star star star

Over the years, the equipment used in our company becomes discontinued, but they’re still of great use to us and our customers. Once these products are no longer available through the manufacturer, finding a reliable, quick supplier is a necessity, and luckily for us, GID Industrial has provided the most trustworthy, quality solutions to our obsolete component needs.

Nidec Vamco

TERRIFIC RESOURCE

star star star star star

This company has been a terrific help to us (I work for Trican Well Service) in sourcing the Micron Ram Memory we needed for our Siemens computers. Great service! And great pricing! I know when the product is shipping and when it will arrive, all the way through the ordering process.

Trican Well Service

GO TO SOURCE

star star star star star

When I can't find an obsolete part, I first call GID and they'll come up with my parts every time. Great customer service and follow up as well. Scott emails me from time to time to touch base and see if we're having trouble finding something.....which is often with our 25 yr old equipment.

ConAgra Foods

Related Products

product

Rockwell Automation 1734-485ASC Serial I/O Modules- Inputs/Outputs 1 Serial Interface channel, Point...

product

Allen Bradley 1734-IA2 Input Module - 120 VAC 2 channel input module

product

Allen Bradley 1734-IB4 Input Module - 24V DC 4 channel sink input module

product

Allen Bradley 1734-OB2 Output Module - 24V DC 2 CHANNEL STANDARD SOURCE OUTPUT MODULE

product

Allen Bradley 1734-OB4 I/O Module - 24V DC 4 CHANNEL STANDARD SOURCE OUTPUT MODULE

product

Allen Bradley 1734-OB4E I/O Module - 4 current sourcing, electronically protected, enhanced sourcing...