M-SYSTEMS M2BD
Specifications
A/D conversion
Accuracy of input module ±0.1%
AC Power Input Power Consumption
approx. 6 VA without I/O module; approx. 30 VA with 4 modules (M2DY); approx. 50 VA with 8 modules; approx. 90 VA with 16 modules
Atmosphere
No corrosive gas or heavy dust
Baud rate setting
DIP switch
Capacity
4, 8 or 16 positions
D/A conversion
Accuracy of M2VS ±0.1 %
DC Power input Current consumption
approx. 0.25 A without I/O module; approx. 1 A with 4 modules (M2DY); approx. 1.5 A with 8 modules; approx. 2.5 A with 16 modules
Dielectric strength
1000 V AC @1 minute (power to I/O module to communication module)
Field I/O
M3 screw terminals (torque 0.8 N•m)
Insulation resistance
Greater than 100 M Omega with 500V DC
Isolation
Field I/O to transmission to power
Mounting
Surface
MS (Module Status) indicator
bi-color (green/red) LED indicates device status.
Node address setting
DIP switch; 00 – 63
NS (Network Status) indicator
bi-color (green/red) LED indicates status of the communication link.
Operating humidity
30 to 90 %RH (non-condensing)
Operating temperature
-5 to +55°C (23 to 131°F)
Power indicator
Green LED turns on with power supplied.
Power input
M3 screw terminals (torque 0.8 N•m)
Power loss time
Less than 10 msec.
Power output
11 – 25 V DC; 60 mA max. at 24 V (supplied from the comm. terminal)
Screw terminal
Nickel-plated steel
Transmission
Terminal block
Transmission cable
approved for DeviceNet
Weight
Without I/O module
Features
- 2000V AC isolation
- Base socket included with modules
- CE marking and UL/C-UL Class 1 Div 2 approval
- Enabling interfacing analog I/Os to DeviceNet
- Fixed range or PC programmable models selectable
- M2 use a compact-size, plug-in socket base for quick installation or replacement of modules without disturbing wiring
- Power supplied through printed wiring on the base
- Receiving up to 16 Mini-M modules
- Selectable 100-240V AC/24V DC power input
- Standard DIN rail or surface mounting
Datasheet
Extracted Text
Model Model Model Model Model Model Model Model Model Model Model Model Model Model Model Model ZERO ZERO ZERO ZERO ZERO ZERO ZERO ZERO ZERO ZERO ZERO ZERO ZERO ZERO ZERO ZERO SPAN SPAN SPAN SPAN SPAN SPAN SPAN SPAN SPAN SPAN SPAN SPAN SPAN SPAN SPAN SPAN MODEL: M2BD Super-mini Signal Conditioners Mini-M Series [4] OPTIONS STANDARDS & APPROVALS blank: Without UL or CE COMMUNICATION CONTROLLER /UL: UL approval (CE marking) (DeviceNet™ use) Functions & Features • Receiving up to 16 Mini-M modules GENERAL SPECIFICATIONS • Enabling interfacing analog I/Os to DeviceNet™ Capacity: 4, 8 or 16 positions • Power supplied through printed wiring on the base Connection • UL approval, CE marking Transmission: Terminal block Field I/O: M3 screw terminals (torque 0.8 N·m) Power input: M3 screw terminals (torque 0.8 N·m) Transmission cable: approved for DeviceNet Screw terminal: Nickel-plated steel Isolation: Field I/O to transmission to power Node address setting: DIP switch; 00 – 63 Baud rate setting: DIP switch 125 kbps (factory default), 250 kbps, 500 kbps Power indicator: Green LED turns on with power supplied. MS (Module Status) indicator: bi-color (green/red) LED indicates device status. NS (Network Status) indicator: bi-color (green/red) LED indicates status of the communication link. MODEL: M2BD–[1][2]-[3][4] INPUT SPECIFICATIONS ORDERING INFORMATION Input modules: Mini-M series; output 1 – 5 V DC; • Code number: M2BD-[1][2]-[3][4] (non-isolated types are not usable.) Specify a code from below for each [1] through [4]. ■ ANALOG INPUT (e.g. M2BD-161-R/UL) Input range: See each I/O module spec. Power input specification for each I/O modules must be the Voltage at the field I/O terminals limited within 30 V DC for same as that of the base. UL. Isolation: transformer (by Mini-M module) A/D conversion output: 16-bit binary [1] CAPACITY Signal range 0 – 100 % is converted into hexadecimal 0000 04: 4 positions – 1770 (0 – 6000). -15 to 0 % is represented by 2’s 08: 8 positions complements. 16: 16 positions Overall range is represented by hexadecimal FC7C – 1AF4 (-900 – +6900), for -15 – +115 %. [2] I/O TYPE 1: Input OUTPUT SPECIFICATIONS 2: Output Output modules: Model M2VS; input 1 – 5 V DC ■ ANALOG OUTPUT [3] POWER INPUT Output range: See model M2VS spec. AC Power Isolation: Transformer K: 85 – 132 V AC (Operational voltage range 85 – 132 V, 47 – 66 Hz) D/A conversion output: 16-bit binary (CE or UL not available) Signal range 0 – 100 % is converted into hexadecimal 0000 DC Power – 1770 (0 – 6000). -15 to 0 % is represented by 2’s R: 24 V DC complements. (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) Overall range is represented by hexadecimal FC7C – 1AF4 (- 900 – +6900), for -15 – +115 %. http://www.m-system.co.jp/ M2BD SPECIFICATIONS ES-5002 Rev.5 Page 1/7 MODEL: M2BD INSTALLATION •AC Power input: Power Consumption: approx. 6 VA without I/O module approx. 30 VA with 4 modules (M2DY) approx. 50 VA with 8 modules approx. 90 VA with 16 modules • DC Power input Current consumption: approx. 0.25 A without I/O module approx. 1 A with 4 modules (M2DY) approx. 1.5 A with 8 modules approx. 2.5 A with 16 modules Power output: 11 – 25 V DC; 60 mA max. at 24 V (supplied from the comm. terminal) Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: Surface Weight: Without I/O module M2BD-04 1.2 kg (2.6 lbs) M2BD-08 1.5 kg (3.3 lbs) M2BD-16 2 kg (4.4 lbs) PERFORMANCE in percentage of span A/D conversion: Accuracy of input module ±0.1% D/A conversion: Accuracy of M2VS ±0.1 % Power loss time: ≤ 10 msec. Insulation resistance: ≥ 100 MΩ with 500V DC Dielectric strength: 1000 V AC @1 minute (power to I/O module to communication module) STANDARDS & APPROVALS CE conformity: EMC Directive (2004/108/EC) EMI EN 61000-6-4 EMS EN 61000-6-2 Low Voltage Directive (2006/95/EC) EN 61010-1 Measurement Category II Pollution Degree 2 Max. operating voltage 300V Input or output to power: Reinforced insulation Input to output: Basic insulation Approval: UL/C-UL nonincendive Class I, Division 2, Groups A, B, C, and D hazardous locations (UL 1604, CAN/CSA-C22.2 No.213); UL/C-UL general safety requirements (UL 3111-1, CAN/CSA-C22.2 No.1010-1) http://www.m-system.co.jp/ M2BD SPECIFICATIONS ES-5002 Rev.5 Page 2/7 MODEL: M2BD COMM. MODULE FRONT PANEL Modular Jack Power LED MS Indicator LED NS Indicator LED PWR MS NS NA0 NA1 Node NA2 Address NA3 Setting NA4 NA5 Baud Rate DR0 Terminal Block DR1 Setting ON Refer to the instruction manual for detailed precedures. http://www.m-system.co.jp/ M2BD SPECIFICATIONS ES-5002 Rev.5 Page 3/7 MODEL: M2BD DIMENSIONS unit: mm (inch) ■ M2BD-041 (INPUT BASE) 210 (8.27) 190 (7.48) 170 (6.69) 1 2 3 4 5 8 5 8 5 8 5 8 FG1 1 4 1 4 1 4 1 4 13 14 CH1 CH4 2–M3 POWER TERMINALS CT PROTECTOR (CTM2) 6 (.24) 16–M3 INPUT TERMINALS *165 (6.50) required for pneumatic tubing for M2PV. ■ M2BD-042 (OUTPUT BASE) 210 (8.27) 190 (7.48) 170 (6.69) 6 (.24) 8–M3 OUTPUT TERMINALS CH1 CH2 CH3 CH4 9 12 9 12 9 12 9 12 1 2 3 4 FG1 13 14 2–M3 POWER TERMINALS http://www.m-system.co.jp/ M2BD SPECIFICATIONS ES-5002 Rev.5 Page 4/7 130 (5.12) 130 (5.12) 130 (5.12) 130 (5.12) 100 (3.94) 125 (4.92) 125 (4.92)* 100 (3.94) 27 (1.06) MODEL: M2BD ■ M2BD-081 (INPUT BASE) 300 (11.81) 280 (11.02) 260 (10.24) 1 2 3 4 5 6 7 8 5 8 5 8 5 8 5 8 5 8 5 8 5 8 5 8 FG1 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 13 14 CH1 CH7 CH8 2–M3 POWER TERMINALS CT PROTECTOR (CTM2) 6 (.24) 32–M3 INPUT TERMINALS *165 (6.50) required for pneumatic tubing for M2PV. ■ M2BD-082 (OUTPUT BASE) 300 (11.81) 280 (11.02) 260 (10.24) 6 (.24) 16–M3 OUTPUT TERMINALS CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 9 12 9 12 9 12 9 12 9 12 9 12 9 12 9 12 1 2 3 4 5 6 7 8 FG1 13 14 2–M3 POWER TERMINALS http://www.m-system.co.jp/ M2BD SPECIFICATIONS ES-5002 Rev.5 Page 5/7 130 (5.12) 130 (5.12) 130 (5.12) 130 (5.12) 125 (4.92) 100 (3.94) 125 (4.92)* 100 (3.94) 27 (1.06) MODEL: M2BD ■ M2BD-161 (INPUT BASE) 480 (18.90) 460 (18.11) 440 (17.32) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 5 8 5 8 5 8 5 8 5 8 5 8 FG1 5 8 5 8 5 8 5 8 5 8 5 8 5 8 5 8 5 8 5 8 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 13 14 CH1 CH5 CH6 CH10 CH11 CH16 2–M3 POWER TERMINALS CT PROTECTOR (CTM2) 6 (.24) 64–M3 INPUT TERMINALS *165 (6.50) required for pneumatic tubing for M2PV. ■ M2BD-162 (OUTPUT BASE) 480 (18.90) 460 (18.11) 440 (17.32) 6 (.24) 32–M3 OUTPUT TERMINALS CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH9 CH10 CH11 CH12 CH13 CH14 CH15 CH16 9 12 9 12 9 12 9 12 9 12 9 12 9 12 9 12 9 12 9 12 9 12 9 12 9 12 9 12 9 12 9 12 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 FG1 13 14 2–M3 POWER TERMINALS http://www.m-system.co.jp/ M2BD SPECIFICATIONS ES-5002 Rev.5 Page 6/7 130 (5.12) 130 (5.12) 130 (5.12) 130 (5.12) 125 (4.92) 100 (3.94) 100 (3.94) 125 (4.92)* 27 (1.06) MODEL: M2BD MOUNTING REQUIREMENTS unit: mm (inch) ■ M2BD-04 190 (7.48) 4–M5 SCREW ■ M2BD-08 280 (11.02) 4–M5 SCREW ■M2BD16 460 (18.11) 4–M5 SCREW SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM �INPUT BASE �OUTPUT BASE COMMUNICATION MODULE I/O MODULES 1 ISOLATION INDCATOR 4 9 Ch.1 Ch.1 LED DIP SW V+ INPUT OUTPUT 5 12 CAN_H 8 To Other Communication DeviceNet CPU Drain Devices CAN_L 1 ISOLATION V– 4 9 Ch.2 Ch.2 A / D I / O INPUT OUTPUT 5 12 or CPU D / A 8 Conv. MODULAR JACK PU-2� SERIAL 1 TRANSMISSION ISOLATION LINE 4 9 Ch.16 Ch.16 INPUT OUTPUT 5 12 8 U(+) 13 POWER V(–) 14 Specifications are subject to change without notice. http://www.m-system.co.jp/ M2BD SPECIFICATIONS ES-5002 Rev.5 Page 7/7 100 (3.94) 100 (3.94) 100 (3.94)
Frequently asked questions
How does Industrial Trading differ from its competitors?

Is there a warranty for the M2BD?

Which carrier will Industrial Trading use to ship my parts?

Can I buy parts from Industrial Trading if I am outside the USA?

Which payment methods does Industrial Trading accept?

Why buy from GID?

Quality
We are industry veterans who take pride in our work

Protection
Avoid the dangers of risky trading in the gray market

Access
Our network of suppliers is ready and at your disposal

Savings
Maintain legacy systems to prevent costly downtime

Speed
Time is of the essence, and we are respectful of yours
What they say about us
FANTASTIC RESOURCE
One of our top priorities is maintaining our business with precision, and we are constantly looking for affiliates that can help us achieve our goal. With the aid of GID Industrial, our obsolete product management has never been more efficient. They have been a great resource to our company, and have quickly become a go-to supplier on our list!
Bucher Emhart Glass
EXCELLENT SERVICE
With our strict fundamentals and high expectations, we were surprised when we came across GID Industrial and their competitive pricing. When we approached them with our issue, they were incredibly confident in being able to provide us with a seamless solution at the best price for us. GID Industrial quickly understood our needs and provided us with excellent service, as well as fully tested product to ensure what we received would be the right fit for our company.
Fuji
HARD TO FIND A BETTER PROVIDER
Our company provides services to aid in the manufacture of technological products, such as semiconductors and flat panel displays, and often searching for distributors of obsolete product we require can waste time and money. Finding GID Industrial proved to be a great asset to our company, with cost effective solutions and superior knowledge on all of their materials, it’d be hard to find a better provider of obsolete or hard to find products.
Applied Materials
CONSISTENTLY DELIVERS QUALITY SOLUTIONS
Over the years, the equipment used in our company becomes discontinued, but they’re still of great use to us and our customers. Once these products are no longer available through the manufacturer, finding a reliable, quick supplier is a necessity, and luckily for us, GID Industrial has provided the most trustworthy, quality solutions to our obsolete component needs.
Nidec Vamco
TERRIFIC RESOURCE
This company has been a terrific help to us (I work for Trican Well Service) in sourcing the Micron Ram Memory we needed for our Siemens computers. Great service! And great pricing! I know when the product is shipping and when it will arrive, all the way through the ordering process.
Trican Well Service
GO TO SOURCE
When I can't find an obsolete part, I first call GID and they'll come up with my parts every time. Great customer service and follow up as well. Scott emails me from time to time to touch base and see if we're having trouble finding something.....which is often with our 25 yr old equipment.
ConAgra Foods