ALLEN-BRADLEY 1734-OW4

Image of ALLEN-BRADLEY 1734-OW4

Description

Allen Bradley 1734-OW4 I/O Module - 4 Form A N.O. relays, Digital Contact Output Module

Part Number

1734-OW4

Price

Request Quote

Manufacturer

ALLEN-BRADLEY

Lead Time

Request Quote

Category

PLC

Specifications

Bounce Time

1.2ms (mean)

Category

2

Conducted RF Immunity

10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Conductors Wire Size

14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or stranded copper wire rated at 75°C or greater 3/64 inch (1.2mm) insulation maximum

Customer load to logic

Tested to withstand 2550V dc for 60s, Tested to withstand 2550V dc for 60s

Dimensions Inches

(Millimeters)2.21H x 0.47W x 2.97L(56H x 12W x 75.5L)

EFT/B Immunity

±4kV at 2.5kHz on signal ports, ±4kV at 2.5kHz on power ports

Emissions

CISPR 11 Group 1, Class A

Enclosure Type Rating

None (open-style)

ESD immunity

6kV contact discharges, 8kV air discharges

Expected Life of Electrical Contacts

Minimum 100,000 operations @ rated loads

Indicators

4 yellow output status indicators

Initial Contact Resistance

30m

Isolation Voltage

Between any 2 sets of contacts

Keyswitch Position

7

Mass

1.64 oz/46.5 grams

Minimum Contact Load

100µA at 100mV dc

Module Location

1734-TB or -TBS wiring base assembly

Off-State Leakage Current (max at 240V ac)

1.2mA and bleed resistor thru snubber circuit]

Operate/Release Time

10ms max

Operational Temperature

-20 to 55°C (-4 to 131°F)

Output Current Rating (at rated power) Inductive

2.0A steady state @ 5-28.8V dc, L/R - 7ms

Output Current Rating (at rated power)Resistive

2A @ 5-28.8V dc, 0.5A @ 48V dc, 0.25A @ 125V dc, 2A @ 125V ac, 2A @ 240V ac

Output Signal Delay OFF to ON

10ms maximum (time from valid output on signal to relay

Output Signal Delay ON to OFF

26ms maximum (time from valid output off signal to relay deenergization by module)

Output Voltage Range (load dependent)

5-28.8V dc @ 2.0A resistive, 48V dc @ 0.5A resistive, 125V dc @ 0.25A resistive, 125V ac @ 2.0A resistive, 240V ac @ 2.0A resistive

Outputs per Module

4 Form A isolated (normally open) electromechanical relays

POINTBus current

80mA max @ 5V dc

Power dissipation

0.5W max

Power Rating (steady state)

250W max. for 125V ac resistive output, 480W max. for 240V ac resistive output, 60W max. for 28.8V dc resistive output, 24W max. for 48V dc resistive output, 31W max. for 125V dc resistive output, 250VA max. for 125V ac inductive output, 480VA max. for 240V ac inductive output, 60VA max. for 28.8V dc inductive output, 24VA max. for 48V dc inductive output, 31VA max. for 125V dc inductive output

Radiated RF Immunity

10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz 10V/m with 200Hz 50% Pulse 100%AM at 900Mhz 10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz

Relative Humidity

5 to 95% noncondensing

Shock

operating:30g peak acceleration, Non-operating:50g peak acceleration

Storage Temperature

-40 to 85°C (-40 to 185°F)

Supply Current

2A per channel maximum, 8A per module

Surge Transient Immunity

±1kV line-line(DM) and ±2kV line-earth(CM) on power and

Switching Frequency

1 operation/3s (0.3Hz at rated load) max

Terminal base screw torque

7 pound-inches (0.8Nm)

Thermal Dissipation

1.7 BTU/hr max

Vibration

Tested 5g @ 10-500Hz

Voltage Range

240V ac max

Datasheet

pdf file

allen bradley=1734-ow2_ow4=datashee-1903206617t.pdf

744 KiB

Extracted Text

Installation Instructions POINT I/O 2 or 4 Relay Output Module (Cat. No. 1734-OW2 and 1734-OW4, Series C) 9 4 5 3 6 2 8 7 10 1 Description Description 1 1 6 RTB Removal Handle Mounting Base 1 2 Mechanical Keying (orange) 7 Removable Terminal Block (RTB) 3 Module Wiring Diagram 8 DIN Rail Locking Screw (orange) 4 Module Locking Mechanism 9 Slide-in Writable Label 5 Insertable I/O Module 10 Interlocking Side Pieces 1 Wiring Base Assembly consists of item 1) mounting base, 1734-MB and item 7) removable terminal block, 1734-RTB or -RTBS. POINT I/O is a trademark of Rockwell Automation1 DeviceNet is a trademark of ODVA, Inc. Publication 1734-IN055D-EN-P - April 2004 Module Status Network Status NODE: 0 1 2 3 2 POINT I/O 2 or 4 Relay Output Module This Series C product can be used with DeviceNet and PROFIBUS adapters. It can be used with ControlNet and Ethernet adapters using RSLogix 5000, version 11 (or higher) software. Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.ab.com/manuals/gi) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited. Throughout this manual we use notes to make you aware of safety considerations. Publication 1734-IN055D-EN-P - April 2004 POINT I/O 2 or 4 Relay Output Module 3 Important User Information Identifies information about practices or circumstances that WARNING can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. Identifies information about practices or circumstances that ATTENTION can lead to personal injury or death, property damage, or economic loss. Attentions help you: • identify a hazard • avoid a hazard • recognize the consequence Identifies information that is critical for successful IMPORTANT application and understanding of the product. Publication 1734-IN055D-EN-P - April 2004 4 POINT I/O 2 or 4 Relay Output Module Environment and Enclosure ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as "open type" equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, see the appropriate sections in this publication, as well as the Allen-Bradley publication 1770-4.1 ("Industrial Automation Wiring and Grounding Guidelines"), for additional installation requirements pertaining to this equipment. POINT I/O is grounded through the DIN rail to chassis ATTENTION ground. Use zinc plated, yellow chromated steel DIN rail to assure proper grounding. Using other DIN rail materials (e.g. aluminum, plastic, etc.) which can corrode, oxidize or are poor conductors can result in improper or intermittent platform grounding. Publication 1734-IN055D-EN-P - April 2004 POINT I/O 2 or 4 Relay Output Module 5 EXPLOSION HAZARD WARNING • Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous. • Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product. • Substitution of components may impair suitability for Class I, Division 2. • If this product contains batteries, they must only be changed in an area known to be nonhazardous. Preventing Electrostatic Discharge ATTENTION This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • Touch a grounded object to discharge potential static. • Wear an approved grounding wriststrap. • Do not touch connectors or pins on component boards. • Do not touch circuit components inside the equipment. • If available, use a static-safe workstation. • When not in use, store the equipment in appropriate static-safe packaging. Publication 1734-IN055D-EN-P - April 2004 6 POINT I/O 2 or 4 Relay Output Module Installing the Mounting Base To install the mounting base on the DIN rail, proceed as follows. 1. Position the mounting base vertically above the installed units (adapter, power supply or existing module. 2. Slide the mounting base down allowing the interlocking side pieces to engage the adjacent module or adapter. 3. Press firmly to seat the mounting base on the DIN rail. The mounting base will snap into place. 4. To remove the mounting base from the DIN rail, remove the module, and use a small bladed screwdriver to rotate the base locking screw to a vertical position. This releases the locking mechanism. Then lift straight up to remove. Installing the I/O Module The module can be installed before, or after base installation. Make sure that the mounting base is correctly keyed before installing the module into the mounting base. In addition, make sure the mounting base locking screw is positioned horizontal referenced to the base. When you insert or remove the module while WARNING backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. 1. Using a bladed screwdriver, rotate the keyswitch (2) on the mounting base clockwise until the number 7 aligns with the notch in the base. 2. Make certain the DIN rail locking screw is in the horizontal position. (You cannot insert the module if the locking mechanism is unlocked.) 3. Insert the module straight down into the mounting base and press to secure. The module will lock into place. Publication 1734-IN055D-EN-P - April 2004 POINT I/O 2 or 4 Relay Output Module 7 Installing the Removable Terminal Block (RTB) A removable terminal block is supplied with your wiring base assembly. To remove, pull up on the RTB handle. This allows the mounting base to be removed and replaced as necessary without removing any of the wiring. To reinsert the removable terminal block, proceed as follows. 1. Insert the end opposite the handle into the base unit. This end has a curved section that engages with the wiring base. 2. Rotate the terminal block into the wiring base until it locks itself in place. 3. If an I/O module is installed, snap the RTB handle into place on the module. When you connect or disconnect the Removable WARNING Terminal Block (RTB) with field side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Removing a Mounting Base To remove a mounting base, you must remove any installed module, and the module installed in the base to the right. Remove the removable terminal block (if wired). 1. Unlatch the RTB handle on the I/O module. 2. Pull on the RTB handle to remove the removable terminal block. Publication 1734-IN055D-EN-P - April 2004 8 POINT I/O 2 or 4 Relay Output Module When you connect or disconnect the Removable WARNING Terminal Block (RTB) with field side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. 3. Press on the module lock on the top of the module. 4. Pull on the I/O module to remove from the base. When you insert or remove the module while WARNING backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. 5. Repeat steps 1, 2, 3 and 4 for the module to the right. 6. Use a small bladed screwdriver to rotate the orange base locking screw to a vertical position. This releases the locking mechanism. 7. Then lift straight up to remove. Publication 1734-IN055D-EN-P - April 2004 POINT I/O 2 or 4 Relay Output Module 9 Communicating with Your Module I/O messages are sent to (consumed) and received from (produced) the POINT I/O modules. These messages are mapped into the processor’s memory. This POINT I/O output module does not produce input data (scanner Rx). It does consume 1 byte of I/O data (scanner Tx). Default Data Map for the 1734-OW2 Input Module Message size: 1 Byte 7 6 5 4 3 2 1 0 Consumes Not used Ch1 Ch0 Channel state (scanner Tx) Where: 0 = Off, 1 = On Default Data Map for the 1734-OW4 Input Module Message size: 1 Byte 7 6 5 4 3 2 1 0 Consumes Not used Ch3 Ch2 Ch1 Ch0 Channel state (scanner Tx) Where: 0 = Off, 1 = On Publication 1734-IN055D-EN-P - April 2004 10 POINT I/O 2 or 4 Relay Output Module Wiring the Relay Output Module 1734-OW2 1734-OW4 Module Status Module Module Status Status Network Status Network Network Status Status NODE: NODE: Relay Relay Output Output Status of Output 0 0 0 Status of Output 1 1 1 Status of Output 2 2 Status of Output 3 3 1734 1734 OW2 OW4 Output 0A Output 1A Output 0A Output 1A Output 0B Output 1B Output 0B Output 1B C C Output 2A Output 3A C = Common V V Output 2B Output 3B V = Supply 41974 Relay contacts are not directly powered by the internal ATTENTION power bus. Load power from the internal power bus is available for the 1734-OW2 only. (Connect to pins 6 and 7 for V supply, and 4 and 5 for V common.) Load power must be provided by an external power source for the 1794-OW4. The 1734-OW4 module cannot be powered from the internal power bus. Publication 1734-IN055D-EN-P - April 2004 POINT I/O 2 or 4 Relay Output Module 11 1734-OW2 Load powered by Internal Power Bus 0 1 Out 0A Out 1A Load 2 3 Out 0B Out 1B Load 4 5 C C 6 7 V V Out = Output channel relay contacts 42018 V = Supply (can range from +5V dc to 240V ac) C = Common Channel Output Common Supply 0A 0 4 6 0B 2 4 6 1A 1 5 7 1B 3 5 7 Supply voltage can range from +5V dc to 240V ac, depending on relay load. 12/24V dc power for the module is provided by the internal power bus. Publication 1734-IN055D-EN-P - April 2004 12 POINT I/O 2 or 4 Relay Output Module 1734-OW2 Load powered by External Power 0 1 Power Power Out 0A Out 1A Supply Supply 2 3 Out 0B Out 1B 4 5 C C Load Load 6 7 V V Out = Output channel relay contacts Power Supply = can range from +5V dc to 240V ac C = Common 1 Channel Output Common Supply 0A 0 0B 2 1A 1 1B 3 1 Supply voltage can range from +5V dc to 240V ac, depending on relay load. 12/24V dc power for the module is provided by the external power supply. Publication 1734-IN055D-EN-P - April 2004 POINT I/O 2 or 4 Relay Output Module 13 1734-OW4 Load powered by External Power 0 1 Power Power Out 0A Out 1A Supply Supply 2 3 Out 0B Out 1B Load Load 4 5 Out 3A Power Out 2A Power Supply Supply 6 7 Out 2B Out 3B Load Load Out = Output channel relay contacts 1 Channel Output Common Supply 0A 0 0B 2 1A 1 1B 3 2A 4 2B 6 3A 5 3B 7 1 Supply voltage can range from +5V dc to 240V ac, depending on relay load. 12/24V dc power for the module is provided by the external power supply. Note: The power supply voltage may be daisychained from a 1734 adapter, 1734-FPD or 1734-EP24DC communication interface. Each channel is individually isolated and may have a unique supply and/or voltage as necessary. Publication 1734-IN055D-EN-P - April 2004 14 POINT I/O 2 or 4 Relay Output Module ATTENTION • Do not attempt to increase load current or wattage capability beyond the maximum rating by connecting 2 or more outputs in parallel. The slightest variation in relay switching time may cause one relay to momentarily switch the total load current. • Make certain that all relay wiring is properly connected before applying any power to the module. • Total current draw through the wiring base unit is limited to 10A. Separate power connections to the terminal base unit may be necessary. • Use the end cap from your adapter or interface module to cover the exposed interconnections on the last mounting base on the DIN rail. Failure to do so could result in equipment damage or injury from electric shock. PDN OW2 OW2 PDN IB2 IV2 IB4 IV4 FPD OW2 OW2 OW2 01 01 01 01 01 01 01 01 0101 0 1 0 1 ac power bus 120V ac CV L1 L2/N Wiring with ac Wiring Using a 1734-FPD to Modules only Create a New ac Power Bus Publication 1734-IN055D-EN-P - April 2004 POINT I/O 2 or 4 Relay Output Module 15 IB2 IB4 IV2 IV4 OW2 OW2 OW2 PDN 01 01 01 01 01 01 01 01 24V 42010 L1 L2/N 120V ac/240V ac Wiring using external power source for ac Relay power Publication 1734-IN055D-EN-P - April 2004 16 POINT I/O 2 or 4 Relay Output Module Troubleshooting with the Indicators 1734-OW2 1734-OW4 Module Module Status Module Status Status Network Status Network Network Status Status NODE: NODE: Relay Relay Output Output Status of Output 0 0 0 Status of Output 1 1 1 Status of Output 2 2 Status of Output 3 3 1734 OW2 1734 OW4 41974 Module Status Off No power applied to device Green Device operating normally Flashing Green Device needs commissioning due to configuration missing, incomplete or incorrect. Flashing Red Recoverable fault. Red Unrecoverable fault may require device replacement Flashing Red/Green Device is in self-test Indicator Indication Probable Cause Network Status Off Device is not on-line - Device has not completed dup_MAC_id test. - Device not powered - check module status indicator Flashing Green Device is on-line but has no connections in the established state. Publication 1734-IN055D-EN-P - April 2004 POINT I/O 2 or 4 Relay Output Module 17 Green Device on-line and has connections in the established state. Flashing Red One or more I/O connections in timed-out state Red Critical link failure - failed communication device. Device detected error that prevents it communicating on the network. Flashing Communication faulted device - the device has Red/Green detected a network access error and is in communication faulted state. Device has received and accepted an Identify Communication Faulted Request - long protocol message. Indicator Indication Probable Cause I/O Status Off Outputs off. Yellow Outputs on. Publication 1734-IN055D-EN-P - April 2004 18 POINT I/O 2 or 4 Relay Output Module Safety Approvals North American Hazardous Location Approval The following modules are North American Hazardous Location approved: 1734-OW2 and 1734-OW4. The following information applies when Informations sur l’utilisation de cet équipement operating this equipment in hazardous en environnements dangereux: locations: Products marked “CL I, DIV 2, GP A, B, C, D” are suitable Les produits marqués “CL I, DIV 2, GP A, B, C, D” ne conviennent for use in Class I Division 2 Groups A, B, C, D, Hazardous qu’à une utilisation en environnements de Classe I Division 2 Locations and nonhazardous locations only. Each product Groupes A, B, C, D dangereux et non dangereux. Chaque produit is supplied with markings on the rating nameplate est livré avec des marquages sur sa plaque d’identification qui indicating the hazardous location temperature code. When indiquent le code de température pour les environnements combining products within a system, the most adverse dangereux. Lorsque plusieurs produits sont combinés dans un temperature code (lowest “T” number) may be used to système, le code de température le plus défavorable (code de help determine the overall temperature code of the température le plus faible) peut être utilisé pour déterminer le system. Combinations of equipment in your system are code de température global du système. Les combinaisons subject to investigation by the local Authority Having d’équipements dans le système sont sujettes à inspection par Jurisdiction at the time of installation. les autorités locales qualifiées au moment de l’installation. EXPLOSION HAZARD - RISQUE D’EXPLOSION – AVERTISSEMENT WARNING • Do not disconnect equipment unless • Couper le courant ou s’assurer que power has been removed or the area l’environnement est classé non is known to be nonhazardous. dangereux avant de débrancher • Do not disconnect connections to l'équipement. this equipment unless power has • Couper le courant ou s'assurer que been removed or the area is known l’environnement est classé non to be nonhazardous. Secure any dangereux avant de débrancher les external connections that mate to connecteurs. Fixer tous les this equipment by using screws, connecteurs externes reliés à cet sliding latches, threaded équipement à l'aide de vis, loquets connectors, or other means provided coulissants, connecteurs filetés ou with this product. autres moyens fournis avec ce produit. • Substitution of components may • La substitution de composants peut impair suitability for Class I, Division rendre cet équipement inadapté à une 2. utilisation en environnement de Classe • If this product contains batteries, 1, Division 2. they must only be changed in an • S’assurer que l’environnement est area known to be nonhazardous. classé non dangereux avant de changer les piles. Publication 1734-IN055D-EN-P - April 2004 POINT I/O 2 or 4 Relay Output Module 19 European Hazardous Location Approval The following modules are European Zone 2 approved: 1734-OW2 and 1734-OW4. European Zone 2 Certification (The following applies when the product bears the EEx Marking) This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC. DEMKO certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres, given in Annex II to this Directive. The examination and test results are recorded in EC-type-examination certificate DEMKO 04 ATEX 0330347 X. Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 50021. Observe the following additional Zone 2 certification IMPORTANT requirements. • This equipment is not resistant to sunlight or other sources of UV radiation. • The secondary of a current transformer shall not be open-circuited when applied in Class I, Zone 2 environments. • Equipment of lesser Enclosure Type Rating must be installed in an enclosure providing at least IP54 protection when applied in Class I, Zone 2 environments. • This equipment shall be used within its specified ratings defined by Allen-Bradley. • Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40% when applied in Class I, Zone 2 environments Publication 1734-IN055D-EN-P - April 2004 20 POINT I/O 2 or 4 Relay Output Module Specifications Specifications - 1734-OW2 and -OW4 Output Relay Module Outputs per Module 1734-OW2 - 2 Form A isolated (normally open) electromechanical relays 1734-OW4 - 4 Form A isolated (normally open) electromechanical relays Off-State Leakage 1.2mA and bleed resistor thru snubber circuit Current (max at 240V ac) Output Voltage Range (load 5-28.8V dc @ 2.0A resistive dependent) 48V dc @ 0.5A resistive 125V dc @ 0.25A resistive 125V ac @ 2.0A resistive 240V ac @ 2.0A resistive Output Current Rating Resistive (at rated power) 2A @ 5-28.8V dc 0.5A @ 48V dc 0.25A @ 125V dc 2A @ 125V ac 2A @ 240V ac Inductive 2.0A steady state @ 5-28.8V dc, L/R = 7ms 0.5A steady state @ 48V dc, L/R = 7ms 0.25A steady state @ 125V dc, L/R = 7ms 2.0A steady state, 15A make @ 125V ac, PF = cos θ = 0.4 2.0A steady state, 15A make @ 240V ac, PF = cos θ = 0.4 Power Rating 250W max. for 125V ac resistive output (steady state) 480W max. for 240V ac resistive output 60W max. for 28.8V dc resistive output 24W max. for 48V dc resistive output 31W max. for 125V dc resistive output 250VA max. for 125V ac inductive output 480VA max. for 240V ac inductive output 60VA max. for 28.8V dc inductive output 24VA max. for 48V dc inductive output 31VA max. for 125V dc inductive output Output Signal Delay OFF to ON 10ms maximum (time from valid output on signal to relay energization by module) ON to OFF 26ms maximum (time from valid output off signal to relay deenergization by module) Initial Contact Resistance 30mΩ Switching Frequency 1 operation/3s (0.3Hz at rated load) max Operate/Release Time 10ms max Bounce Time 1.2ms (mean) Minimum Contact Load 100µA at 100mV dc Publication 1734-IN055D-EN-P - April 2004 POINT I/O 2 or 4 Relay Output Module 21 Expected Life of Minimum 100,000 operations @ rated loads Electrical Contacts Fusing Module outputs are not fused. If fusing is desired, you must supply external fusing. Indicators 1 green/red network status indicator, logic side 1 green/red module status indicator, logic side 1734-OW2 - 2 yellow output status indicators 1734-OW4 - 4 yellow output status indicators Keyswitch position 7 General Specifications Module Location 1734-TB or -TBS wiring base assembly Pointbus Current 80mA max @ 5V dc Power Dissipation 0.5W max Thermal Dissipation 1.7 BTU/hr max Isolation Voltage Between any 2 sets Tested to withstand 2550V dc for 60s of contacts Customer load to logic Tested to withstand 2550V dc for 60s Field Power Bus Supply Voltage None required Voltage Range 240V ac max Supply Current 1734-OW2 - 2A per channel maximum, 4A per module 1734-OW4 - 2A per channel maximum, 8A per module Dimensions Inches 2.21H x 0.47W x 2.97L (Millimeters) (56H x 12W x 75.5L) Environmental Conditions Operational Temperature IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20 to 55°C (-4 to 131°F) Storage Temperature IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): -40 to 85°C (-40 to 185°F) Relative Humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat): 5 to 95% noncondensing Shock IEC 60068-2-27 (Test Ea, Unpackaged Shock) Operating 30g peak acceleration Non-operating 50g peak acceleration Vibration IEC 60068-2-6, (Test Fc, Operating) Tested 5g @ 10-500Hz ESD Immunity IEC 61000-4-2: 6kV contact discharges 8kV air discharges Publication 1734-IN055D-EN-P - April 2004 22 POINT I/O 2 or 4 Relay Output Module Radiated RF Immunity IEC 61000-4-3: 10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz 10V/m with 200Hz 50% Pulse 100%AM at 900Mhz 10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz EFT/B Immunity IEC 61000-4-4: ±4kV at 2.5kHz on signal ports ±4kV at 2.5kHz on power ports Surge Transient Immunity IEC 61000-4-5: ±1kV line-line(DM) and ±2kV line-earth(CM) on power and signal ports Conducted RF Immunity IEC 61000-4-6: 10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz Emissions CISPR 11 Group 1, Class A Enclosure Type Rating None (open-style) 2 2 Conductors Wire Size 14 AWG (2.5mm ) - 22 AWG (0.25mm ) solid or stranded copper wire rated at 75°C or greater 3/64 inch (1.2mm) insulation maximum Category 1 2 Terminal Base Screw Torque 7 pound-inches (0.8Nm) Field Wiring Terminations - 0 - Output 0A 1 - Output 1A 1734-OW2 2 - Output 0B 3 - Output 1B 4 - Common 5 - Common 6 - Supply 7 - Supply Field Wiring Terminations - 0 - Output 0A 1 - Output 1A 1734-OW4 2 - Output 0B 3 - Output 1B 4 - Output 2A 5 - Output 3A 6 - Output 2B 7 - Output 3B Mass 1734-OW2 - 1.30 oz/36.9 grams 1734-OW4 - 1.64 oz/46.5 grams Publication 1734-IN055D-EN-P - April 2004 POINT I/O 2 or 4 Relay Output Module 23 Certifications (when C-UL-US - UL Listed Industrial Control Equipment, product is marked) certified for US and Canada C-UL-US - UL Listed for Class I, Division 2, Groups A, B, C and D Hazardous locations, certified for US and Canada 2 EEx European Union 94/9/EEC ATEX Directive, compliant with: EN 50021; Potentially Explosive Atmospheres, Protection “n” (Zone 2) when used at or below 60V ac or 75V dc. 2 CE European Union 89/336/EEC EMC Directive, compliant with: EN 61000-6-4; Industrial Emissions EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity European Union 73/23/EEC LVD Directive, compliant with: EN 61131-2; Programmable Controllers 2 C-Tick Australian Radiocommunications Act compliant with AS/NZS CISPR 11, Industrial Emissions 1 Use this conductor category information for planning conductor routing as described in publication 1770-4.1, “Industrial Automation Wiring and Grounding Guidelines.” 2 See the Product Certification link at www.ab.com for Declaration of Conformity, Certificates, and other certification details. Publication 1734-IN055D-EN-P - April 2004 Publication 1734-IN055D-EN-P - April 2004 PN 957859-42 Supersedes Publication 1734-IN055C-EN-P - April 2002 © 2004 Rockwell International Corporation. Printed in USA

Frequently asked questions

How does Industrial Trading differ from its competitors?

chervon down
Industrial Trading' parent company, GID Industrial, specializes in procuring industrial parts. We know where to find the rare and obsolete equipment that our customers need in order to get back to business. There are other companies who claim to do what we do, but we're confident that our commitment to quality and value is unparalleled in our field.

Is there a warranty for the 1734-OW4?

chervon down
The warranty we offer will be based on what we negotiate with our suppliers. Sometimes, a part will be sold as-is and without a warranty. Our specialty, single board computers, tend to receive a one-year warranty.

Which carrier will Industrial Trading use to ship my parts?

chervon down
We use FedEx, UPS, DHL, and USPS. We have accounts with each of them and generally ship using one of those, but we can also ship using your account if you would prefer. However, we can use other carriers if it will be more convenient for you.

Can I buy parts from Industrial Trading if I am outside the USA?

chervon down
Industrial Trading will definitely serve you. We work with international clients all the time, and we are familiar with shipping to destinations all across the globe.

Which payment methods does Industrial Trading accept?

chervon down
Visa, MasterCard, Discover, and American Express are all accepted by Industrial Trading. We will also accept payment made with wire transfer or PayPal. Checks will only be accepted from customers in the USA. Terms may available for larger orders, upon approval.

Why buy from GID?

quality

Quality

We are industry veterans who take pride in our work

protection

Protection

Avoid the dangers of risky trading in the gray market

access

Access

Our network of suppliers is ready and at your disposal

savings

Savings

Maintain legacy systems to prevent costly downtime

speed

Speed

Time is of the essence, and we are respectful of yours

What they say about us

FANTASTIC RESOURCE

star star star star star

One of our top priorities is maintaining our business with precision, and we are constantly looking for affiliates that can help us achieve our goal. With the aid of GID Industrial, our obsolete product management has never been more efficient. They have been a great resource to our company, and have quickly become a go-to supplier on our list!

Bucher Emhart Glass

EXCELLENT SERVICE

star star star star star

With our strict fundamentals and high expectations, we were surprised when we came across GID Industrial and their competitive pricing. When we approached them with our issue, they were incredibly confident in being able to provide us with a seamless solution at the best price for us. GID Industrial quickly understood our needs and provided us with excellent service, as well as fully tested product to ensure what we received would be the right fit for our company.

Fuji

HARD TO FIND A BETTER PROVIDER

star star star star star

Our company provides services to aid in the manufacture of technological products, such as semiconductors and flat panel displays, and often searching for distributors of obsolete product we require can waste time and money. Finding GID Industrial proved to be a great asset to our company, with cost effective solutions and superior knowledge on all of their materials, it’d be hard to find a better provider of obsolete or hard to find products.

Applied Materials

CONSISTENTLY DELIVERS QUALITY SOLUTIONS

star star star star star

Over the years, the equipment used in our company becomes discontinued, but they’re still of great use to us and our customers. Once these products are no longer available through the manufacturer, finding a reliable, quick supplier is a necessity, and luckily for us, GID Industrial has provided the most trustworthy, quality solutions to our obsolete component needs.

Nidec Vamco

TERRIFIC RESOURCE

star star star star star

This company has been a terrific help to us (I work for Trican Well Service) in sourcing the Micron Ram Memory we needed for our Siemens computers. Great service! And great pricing! I know when the product is shipping and when it will arrive, all the way through the ordering process.

Trican Well Service

GO TO SOURCE

star star star star star

When I can't find an obsolete part, I first call GID and they'll come up with my parts every time. Great customer service and follow up as well. Scott emails me from time to time to touch base and see if we're having trouble finding something.....which is often with our 25 yr old equipment.

ConAgra Foods

Related Products

product

Allen Bradley 1734-AENT Adapter Module - 24V DC EtherNet/IP Twisted Pair Media I/O Adapter

product

Allen Bradley 1734-IB8 POINT I/O Input Module - 24V DC 8 channel sinking input module

product

Allen Bradley 1734-OW2 I/O Module - 24 VDC, 5…28.8V DC at 2.0 A resistive, Digital Contact Output Mo...