GER-4193A
g
GE Power Systems
SPEEDTRONIC™
Mark VI Turbine
Control System
Walter Barker
Michael Cronin
GE Power Systems
Schenectady, NY
SPEEDTRONIC™ Mark VI Turbine Control System
Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Architecture. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Triple Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
I/O Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
General Purpose I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Application Specific I/O. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Operator Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Software Maintenance Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Communication Link Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Time Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Codes and Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Safety Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Printed Wire Board Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
CE – Electromagnetic Compatibility (EMC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
CE – Low Voltage Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Humidity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Elevation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Gas Contaminants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Dust Contaminants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Seismic Universal Building Code (UBC). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
List of Figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
List of Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
� �
GE Power Systems GER-4193A (10/00) i
SPEEDTRONIC™ Mark VI Turbine Control System
� �
GE Power Systems GER-4193A (10/00) ii
SPEEDTRONIC™ Mark VI Turbine Control System
Introduction Architecture
The SPEEDTRONIC™ Mark VI turbine control The heart of the control system is the Control
is the current state-of-the-art control for GE tur- Module, which is available in either a 13- or 21-
bines that have a heritage of more than 30 years slot standard VME card rack. Inputs are
of successful operation. It is designed as a com- received by the Control Module through termi-
plete integrated control, protection, and moni- nation boards with either barrier or box-type
toring system for generator and mechanical terminal blocks and passive signal conditioning.
drive applications of gas and steam turbines. It is
Each I/O card contains a TMS320C32 DSP
also an ideal platform for integrating all power
processor to digitally filter the data before con-
island and balance-of-plant controls. Hardware
version to 32 bit IEEE-854 floating point format.
and software are designed with close coordina-
The data is then placed in dual port memory
tion between GE’s turbine design engineering
that is accessible by the on-board C32 DSP on
and controls engineering to insure that your con-
one side and the VME bus on the other.
trol system provides the optimum turbine per-
In addition to the I/O cards, the Control
formance and you receive a true “system” solu-
Module contains an “internal” communication
tion. With Mark VI, you receive the benefits of
card, a main processor card, and sometimes a
GE’s unmatched experience with an advanced
flash disk card. Each card takes one slot except
turbine control platform. (See Figure 1.)
for the main processor that takes two slots.
Cards are manufactured with surface-mounted
technology and conformal coated per IPC-CC-
830.
I/O data is transmitted on the VME backplane
between the I/O cards and the VCMI card
located in slot 1. The VCMI is used for “inter-
nal” communications between:
� I/O cards that are contained within its
card rack
� I/O cards that may be contained in
expansion I/O racks called Interface
Modules
• Over 30 years experience � I/O in backup
Protection
Modules
• Complete control, protection, and
� I/O in other Control Modules used in
monitoring
triple redundant control
• Can be used in variety of applications
configurations
� The main processor card
• Designed by GE turbine and controls
engineering
The main processor card executes the bulk of
the application software at 10, 20, or 40 ms
depending on the requirements of the applica-
Figure 1. Benefits of Speedtronic™ Mark VI tion. Since most applications require that spe-
� �
GE Power Systems GER-4193A (10/00) 1
SPEEDTRONIC™ Mark VI Turbine Control System
cific parts of the control run at faster rates (i.e. Protection Module, but it is not required for
servo loops, pyrometers, etc.), the distributed tripping.
processor system between the main processor
and the dedicated I/O processors is very impor- Triple Redundancy
tant for optimum system performance. A QNX
Mark VI control systems are available in
operating system is used for real-time applica-
Simplex and Triple Redundant forms for small
tions with multi-tasking, priority-driven preemp-
applications and large integrated systems with
tive scheduling, and fast-context switching.
control ranging from a single module to many
distributed modules. The name Triple Module
Communication of data between the Control
Redundant (TMR) is derived from the basic
Module and other modules within the Mark VI
architecture with three completely separate and
control system is performed on IONet. The
independent Control Modules, power supplies,
VCMI card in the Control Module is the IONet
and IONets. Mark VI is the third generation of
bus master communicating on an Ethernet
triple redundant control systems that were pio-
10Base2 network to slave stations. A unique pol-
neered by GE in 1983. System throughput
ing type protocol (Asynchronous Drives
enables operation of up to nine, 21-slot VME
Language) is used to make the IONet more
racks of I/O cards at 40 ms including voting the
deterministic than traditional Ethernet LANs.
data. Inputs are voted in software in a scheme
An optional Genius Bus™ interface can be pro-
called Software Implemented Fault Tolerance
vided on the main processor card in Mark VI
(SIFT). The VCMI card in each Control
Simplex controls for communication with the
Module receives inputs from the Control
GE Fanuc family of remote I/O blocks. These
Module back-plane and other modules via “its
blocks can be selected with the same software
own” IONet.
configuration tools that select Mark VI I/O
cards, and the data is resident in the same data-
Data from the VCMI cards in each of the three
base.
Control Modules is then exchanged and voted
prior to transmitting the data to the main
The Control Module is used for control, pro-
processor cards for execution of the application
tection, and monitoring functions, but some
software. Output voting is extended to the tur-
applications require backup protection. For
bine with three coil servos for control valves and
example, backup emergency overspeed protec-
2 out of 3 relays for critical outputs such as
tion is always provided for turbines that do not
hydraulic trip solenoids. Other forms of output
have a mechanical overspeed bolt, and backup
voting are available, including a median select
synch check protection is commonly provided
of 4-20ma outputs for process control and 0-
for generator drives. In these applications, the
200ma outputs for positioners.
IONet is extended to a Backup Protection
Module that is available in Simplex and triple Sensor interface for TMR controls can be either
redundant forms. The triple redundant version single, dual, triple redundant, or combinations
contains three independent sections (power of redundancy levels. The TMR architecture
supply, processor, I/O) that can be replaced supports riding through a single point failure in
while the turbine is running. IONet is used to the electronics and repair of the defective card
access diagnostic data or for cross-tripping or module while the process is running. Adding
between the Control Module and the sensor redundancy increases the fault tolerance
� �
GE Power Systems GER-4193A (10/00) 2
SPEEDTRONIC™ Mark VI Turbine Control System
of the overall “system.” Another TMR feature is has one, fixed, box-type terminal block. It can
2
the ability to distinguish between field sensor accept one 3.0 mm (#12AWG) wire or two 2.0
2
faults and internal electronics faults. mm (#14AWG) wires with 300 volt insulation.
Diagnostics continuously monitor the 3 sets of
I/O devices on the equipment can be mounted
input electronics and alarms any discrepancies
up to 300 meters (984 feet) from the termina-
between them as an internal fault versus a sen-
tion boards, and the termination boards must
sor fault. In addition, all three main processors
be within 15 m (49.2’) from their correspon-
continue to execute the correct “voted” input
ding I/O cards. Normally, the termination
data. (See Figure 2.)
boards are mounted in vertical columns in ter-
mination cabinets with pre-assigned cable
To Other GE
Operator Operator Maintenance / Maintenance
To Other GE
lengths and routing to minimize exposure to
Control Systems Interface
Control Systems Interface
Communications to DCS
Communications To DCS
emi-rfi for noise sensitive signals such as speed
Unit Unit Data Highway Data Highway
1. RS232 Modbus Slave/Master
1. RS232 Modbus Slave/Master
Ethernet Ethernet 2. 2. Ethernet TCP-IP Modbus Slave Ethernet TCP-IP Modbus Slave
R
CIMPLICITY Display System
CIMPLICITY® Display System
3. Ethernet TCP-IP GSM
TM inputs and servo loops.
Windows NT Operating System 3. Ethernet TCP-IPGSM
Windows NT™ Operating System
Backup Protection
Primary Controllers
Backup Protection
1. Emergency Overspeed
Primary Controllers
1. Control 1. Emergency Overspeed
1. Control
2. 2. Synch Check Protection Synch Check Protection
2. Protection General Purpose I/O
2. Protection
3. Monitoring
3. Monitoring
Protection Protection Module Module
Discrete I/O. A VCRC card provides 48 digital
Control Control Module Module
Ethernet Ethernet
P.S.
inputs and 24 digital outputs. The I/O is divid-
P.S.
CPU
X CPU
P
I/O I/O
ed between 2 Termination Boards for the con-
S
tact inputs and another 2 for the relay outputs.
Redundant Unit
Redundant Unit
Data Highway
Data Highway
Ethernet Ethernet - IONet - IONet
(See Table 1.)
(if required) (Required)
Analog I/O. A VAIC card provides 20 analog
Control Control Module Module
P.S.
P.S.
inputs and 4 analog outputs. The I/O is divided
Y CPU
CPU
P
I/O
I/O
S
between 2 Termination Boards. A VAOC is ded-
icated to 16 analog outputs and interfaces with
Ethernet Ethernet - IONet - IONet
1 barrier-type Termination Board or 2 box-type
Control Control Module Module
Termination Boards. (See Table 2.)
P.S.
P.S.
Z CPU CPU
P
Temperature Monitoring. A VTCC card pro-
I/O
I/O
S
vides interface to 24 thermocouples, and a
VRTD card provides interface for 16 RTDs. The
Ethernet Ethernet - IONet - IONet
input cards interface with 1 barrier-type
Figure 2. Mark VI TMR control configuration
TB Type I/O Characteristics
TBCI Barrier 24 CI 70-145Vdc, optical isolation, 1ms SOE
2.5ma/point except last 3 input are 10ma / point
I/O Interface
DTCI Box 24 CI 18-32Vdc, optical isolation, 1ms SOE
2.5ma/point except last 3 input are 10ma/point
There are two types of termination boards. One TICI Barrier 24 CI 70-145Vdc, 200-250Vdc, 90-132Vrms, 190-264Vrms
(47-63Hz), optical isolation 1ms SOE, 3ma / point
TRLY Barrier 12 CO Plug-in, magnetic relays, dry, form “C” contacts
type has two 24-point, barrier-type terminal
6 circuits with fused 3.2A, suppressed solenoid outputs
Form H1B: diagnostics for coil current
blocks that can be unplugged for field mainte-
Form H1C: diagnostics for contact voltage
Voltage Resistive Inductive
nance. These are available for Simplex and
24Vdc 3.0A 3.0 amps L/R = 7 ms, no suppr.
2
3.0 amps L/R = 100 ms, with suppr
TMR controls. They can accept two 3.0 mm
125Vdc 0.6A 0.2 amps L/R = 7 ms, no suppr.
(#12AWG) wires with 300 volt insulation. 0.6 amps L/R = 100 ms, with suppr
120/240Vac 6/3A 2.0 amps pf = 0.4
Another type of termination board used on DRLY Box 12 CO Same as TRLY, but no solenoid circuits
Simplex controls is mounted on a DIN rail and
Table 1. Discrete I/O
� �
GE Power Systems GER-4193A (10/00) 3
Software Voting
Software Voting
SPEEDTRONIC™ Mark VI Turbine Control System
reduced by eliminating peripheral instrumenta-
Analog I/O
tion. The VTUR card is designed to integrate
TB Type I/O Characteristics
several of the unique sensor interfaces used in
TBAI Barrier 10 AI (8) 4-20ma (250 ohms) or +/-5,10Vdc inputs
2 AO (2) 4-20ma (250 ohms) or +/-1ma (500 ohms) inputs
turbine control systems on a single card. In
Current limited +24Vdc provided per input
(2) +24V, 0.2A current limited power sources
some applications, it works in conjunction with
(1) 4-20ma output (500 ohms)
(1) 4-20ma (500 ohms) or 0-200ma (50 ohms) output
the I/O interface in the Backup Protection
TBAO Barrier 16 AO (16) 4-20ma outputs (500 ohms)
DTAI Box 10 AI (8) 4-20ma (250 ohms) or +/-5,10Vdc inputs
Module described below.
2 AO (2) 4-20ma (250 ohms) or +/-1ma (500 ohms) inputs
Current limited +24Vdc available per input
Speed (Pulse Rate) Inputs. Four-speed inputs
(1) 4-20ma output (500 ohms)
(1) 4-20ma (500 ohms) or 0-200ma (50 ohms) output
from passive magnetic sensors are monitored by
DTAO Box 8 AO (8) 4-20ma outputs (500 ohms)
the VTUR card. Another two-speed (pulse rate)
Table 2. Analog I/O
inputs can be monitored by the servo card
VSVO which can interface with either passive or
Termination Board or 2 box-type Termination
active speed sensors. Pulse rate inputs on the
Boards. Capacity for monitoring 9 additional
VSVO are commonly used for flow-divider feed-
thermocouples is provided in the Backup
back in servo loops. The frequency range is 2-
Protection Module. (See Table 3.)
14k Hz with sufficient sensitivity at 2 Hz to
detect zero speed from a 60-toothed wheel. Two
Temperature Monitoring
additional passive speed sensors can be moni-
TB Type I/O Characteristics
TBTC Barrier 24 TC Types: E, J, K, T, grounded or ungrounded
tored by “each” of the three sections of the
H1A fanned (paralleled) inputs, H1B dedicated inputs
DTTC Box 12 TC Types: E, J, K, T, grounded or ungrounded
Backup Protection Module used for emergency
TRTD Barrier 16 RTD 3 points/RTD, grounded or ungrounded
10 ohm copper, 100/200 ohm platinum, 120 ohm nick
overspeed protection on turbines that do not
H1A fanned (paralleled) inputs, H1B dedicated inputs
DTAI Box 8 RTD RTDs, 3 points/RTD, grounded or ungrounded have a mechanical overspeed bolt. IONet is
10 ohm copper, 100/200 ohm platinum, 120 ohm nick
used to communicate diagnostic and process
Table 3. Temperature Monitoring data between the Backup Protection Module
and the Control Module(s) including cross-trip-
ping capability; however, both modules will ini-
Application Specific I/O
tiate system trips independent of the IONet.
In addition to general purpose I/O, the Mark
(See Table 4 and Table 5.)
VI has a large variety of cards that are designed
Synchronizing. The synchronizing system con-
for direct interface to unique sensors and actu-
sists of automatic synchronizing, manual syn-
ators. This reduces or eliminates a substantial
chronizing, and backup synch check protec-
amount of interposing instrumentation in
tion. Two single-phase PT inputs are provided
many applications. As a result, many potential
VTUR I/O Terminations from Control Module
single-point failures are eliminated in the most
TB Type I/O Characteristics
critical area for improved running reliability
TTUR Barrier 4 Pulse rate Passive magnetic speed sensors (2-14k Hz)
2 PTs Single phase PTs for synchronizing
and reduced long-term maintenance. Direct
Synch relays Auto/Manual synchronizing interface
2 SVM Shaft voltage / current monitor
interface to the sensors and actuators also
TRPG* Barrier 3 Trip solenoids (-) side of interface to hydraulic trip solenoids
TRPS* 8 Flame inputs UV flame scanner inputs (Honeywell)
enables the diagnostics to directly interrogate
TRPL*
DTUR Box 4 Pulse Rate Passive magnetic speed sensors (2-14k Hz)
the devices on the equipment for maximum
DRLY Box 12 Relays Form “C” contacts – previously described
DTRT Transition board between VTUR & DRLY
effectiveness. This data is used to analyze device
and system performance. A subtle benefit of Table 4. VTUR I/O terminations from Control
this design is that spare-parts inventories are Module
� �
GE Power Systems GER-4193A (10/00) 4
SPEEDTRONIC™ Mark VI Turbine Control System
Flame Detection. The existence of flame either
VPRO I/O Terminations from Backup Protection Module
can be calculated from turbine parameters that
TB Type I/O Characteristics
TPRO Barrier 9 Pulse rate Passive magnetic speed sensors (2-14k Hz)
are already being monitored or from a direct
2 PTs Single phase PTs for backup synch check
3 Analog inputs (1) 4-20ma (250 ohm) or +/-5,10Vdc inputs
interface to Reuter Stokes or Honeywell-type
(2) 4-20ma (250 ohm)
9 TC inputs Thermocouples, grounded or ungrounded
flame detectors. These detectors monitor the
TREG* Barrier 3 Trip solenoids (+) side of interface to hydraulic trip solenoids
TRES* 8 Trip contact in 1 E-stop (24Vdc) & 7 Manual trips (125Vdc) flame in the combustion chamber by detecting
TREL*
UV radiation emitted by the flame. The Reuter
Table 5. VPRO I/O terminations from Backup
Stokes detectors produce a 4-20ma input. For
Protection Module
Honeywell flame scanners, the Mark VI supplies
the 335Vdc excitation and the VTUR / TRPG
on the TTUR Termination Board to monitor
monitors the pulses of current being generated.
the generator and line busses via the VTUR
This determines if carbon buildup or other
card. Turbine speed is matched to the line fre-
contaminates on the scanner window are caus-
quency, and the generator and line voltages are
ing reduced light detection.
matched prior to giving a command to close the
breaker via the TTUR.
Trip System. On turbines that do not have a
mechanical overspeed bolt, the control can
An external synch check relay is connected in
issue a trip command either from the main
series with the internal K25P synch permissive
processor card to the VTUR card in the Control
relay and the K25 auto synch relay via the
Module(s) or from the Backup Protection
TTUR. Feedback of the actual breaker closing
Module. Hydraulic trip solenoids are wired with
time is provided by a 52G/a contact from the
the negative side of the 24Vdc/125Vdc circuit
generator breaker (not an auxiliary relay) to
connected to the TRPG, which is driven from
update the database. An internal K25A synch
the VTUR in the Control Module(s) and the
check relay is provided on the TTUR; however,
positive side connected to the TREG which is
the backup phase / slip calculation for this relay
driven from the VPRO in each section of the
is performed in the Backup Protection Module
Backup Protection Module. A typical system trip
or via an external backup synch check relay.
initiated in the Control Module(s) will cause
Manual synchronizing is available from an oper-
the analog control to drive the servo valve actu-
ator station on the network or from a synchro-
ators closed, which stops fuel or steam flow and
scope.
de-energizes (or energizes) the hydraulic trip
Shaft Voltage and Current Monitor. Voltage can
solenoids from the VTUR and TRPG. If cross-
build up across the oil film of bearings until a
tripping is used or an overspeed condition is
discharge occurs. Repeated discharge and arc-
detected, then the VTUR/TRPG will trip one
ing can cause a pitted and roughened bearing
side of the solenoids and the VPTRO/TREG
surface that will eventually fail through acceler-
will trip the other side of the solenoid(s).
ated mechanical wear. The VTUR / TTUR can
continuously monitor the shaft-to- ground volt- Servo Valve Interface. A VSVO card provides 4
age and current, and alarm at excessive levels. servo channels with selectable current drivers,
Test circuits are provided to check the alarm feedback from LVDTs, LVDRs, or ratio metric
functions and the continuity of wiring to the LVDTs, and pulse-rate inputs from flow divider
brush assembly that is mounted between the feedback used on some liquid fuel systems. In
turbine and the generator. TMR applications, 3 coil servos are commonly
� �
GE Power Systems GER-4193A (10/00) 5
SPEEDTRONIC™ Mark VI Turbine Control System
used to extend the voting of analog outs to the mination board can be provided with active iso-
servo coils. Two coil servos can also be used. lation amplifiers to buffer the sensor signals
One, two, or three LVDT/Rs feedback sensors from BNC connectors. These connectors can be
can be used per servo channel with a high select, used to access real-time data by remote vibra-
low select, or median select made in software. At tion analysis equipment. In addition, a direct
least 2 LVDT/Rs are recommended for TMR plug connection is available from the termina-
applications because each sensor requires an AC tion board to a Bently Nevada 3500 monitor.
excitation source. (See Table 6 and Table 7.) The 16 vibration inputs, 8 DC position inputs,
and 2 Keyphasor inputs on the VVIB are divid-
TB TB Ty Typ pe e I/O I/O C Ch har arac act te er ri is st ti ic cs s
ed between 2 TVIB termination boards for
T TS SV VO O Barri Barrie er r 2 2 c ch hn nl ls s. . (2 (2) S ) Se erv rvo o c cu urr rre en nt t s so ou ur rces ces
(6 (6) L ) LV VD DT T/ /L LV VD DR R feed feedb ba ac ck k
3,000 rpm and 3,600 rpm applications. Faster
0 0 t to o 7 7. .0 0 V Vr rm ms s
shaft speeds may require faster sampling rates
(4 (4) E ) Ex xc ci it ta at ti io on n s so ou ur rc ce es s
7 7 V Vr rm ms s, , 3. 3.2k Hz 2k Hz
on the VVIB processor, resulting in reduced
( (2 2) ) P Pu ul ls se e r ra at te e i in np pu ut ts s ( (2 2- -14k Hz 14k Hz) )
vibration inputs from 16-to-8. (See Table 8.)
*o *onl nly 2 y 2 pe per r VS VSV VO O
D DS SV VO O Bo Box x 2 2 c ch hn nl ls s. . (2 (2) S ) Se erv rvo o c cu urr rre en nt t s so ou ur rces ces
(6 (6) L ) LV VD DT T/ /L LV VD DR R feed feedb ba ac ck k
0 0 t to o 7 7. .0 0 V Vr rm ms s
VVIB I/O Terminations from Control Module
(2 (2) E ) Ex xc ci it ta at ti io on n s so ou ur rc ce es s
TB Type I/O Characteristics
7 7 V Vr rm ms s, , 3. 3.2k Hz 2k Hz
TVIB Barrier 8 Vibr. Seismic, Proximitor,
( (2 2) ) P Pu ul ls se e r ra at te e i in np pu ut ts s ( (2 2- -14k Hz 14k Hz) )
Velomitor, accelerometer
*o *onl nly 2 y 2 pe per r VS VSV VO O
charge amplifier
Table 6. VSVO I/O terminations from Control
DC inputs
4 Pos.
Module Keyphasor
1 KP
Current limited –24Vdc
provided per probe
Nominal Servo Valve Ratings
Coil Nominal Coil Mark VI
Table 8. VVIB I/O terminations from Control
Type Current Resistance Control
Module
#1 +/- 10 ma 1,000 ohms Simplex & TMR
#2 +/- 20 ma 125 ohms Simplex
#3 +/- 40 ma 62 ohms Simplex
Three phase PT and CT monitoring. The VGEN
#4 +/- 40 ma 89 ohms TMR
card serves a dual role as an interface for 3
#5 +/- 80 ma 22 ohms TMR
#6 +/- 120 ma 40 ohms Simplex
phase PTs and 1 phase CTs as well as a special-
#7 +/- 120 ma 75 ohms TMR
ized control for Power-Load Unbalance and
Table 7. Nominal servo valve ratings
Early-Valve Actuation on large reheat steam tur-
bines. The I/O interface is split between the
TGEN Termination Board for the PT and CT
Vibration / Proximitor® Inputs. The VVIB card
inputs and the TRLY Termination Board for
provides a direct interface to seismic (velocity),
relay outputs to the fast acting solenoids. 4-
Proximitor®, Velomitor®, and accelerometer
20ma inputs are also provided on the TGEN for
(via charge amplifier) probes. In addition, DC
monitoring pressure transducers. If an EX2000
position inputs are available for axial measure-
Generator Excitation System is controlling the
ments and Keyphasor® inputs are provided.
generator, then 3 phase PT and CT data is com-
Displays show the 1X and unfiltered vibration
municated to the Mark VI on the network
levels and the 1X vibration phase angle. -24vdc
rather than using the VGEN card. (See Table 9.)
is supplied from the control to each Proximitor
Optical Pyrometer Inputs. The VPYR card moni-
with current limiting per point. An optional ter-
� �
GE Power Systems GER-4193A (10/00) 6
SPEEDTRONIC™ Mark VI Turbine Control System
� A backup operator interface to the
TB Type I/O Characteristics
plant DCS operator interface
TGEN Barrier 2 PTs 3 Phase PTs, 115Vrms
5-66 Hz, 3 wire, open delta
� A gateway for communication links to
3 CTs 1 Phase CTs, 0-5A
other control systems
(10A over range) 5-66 Hz
4 AI 4-20ma (250 ohms)
� A permanent or temporary
or +/-5,10Vdc inputs
maintenance station
Current limited +24Vdc/input
TRLY Barrier 12 CO Plug-in magnetic relays
� An engineer’s workstation
previously described
Table 9. VGEN I/O terminations from Control
Module
tors two LAND infrared pyrometers to create a
temperature profile of rotating turbine blades.
Separate, current limited +24Vdc and –24Vdc
sources are provided for each Pyrometer that
returns four 4-20ma inputs. Two Keyphasors are
used for the shaft reference. The VPYR and
matching TPYR support 5,100 rpm shaft speeds
and can be configured to monitor up to 92 buck-
ets with 30 samples per bucket. (See Table 10.)
Figure 3. Operator interface graphics:
TB Type I/O Characteristics
TPYR Barrier 2 Pyrometers (8) 4-20ma (100 ohms)
7FA Mark VI
(2) Current limited
+24Vdc sources
All control and protection is resident in the
(2) Current limited
Mark VI control, which allows the HMI to be a
-24Vdc sources
non-essential component of the control system.
(2) Keyphasor inputs
It can be reinitialized or replaced with the
Table 10. VPYR I/O terminations from Control
process running with no impact on the control
Module
system. The HMI communicates with the main
processor card in the Control Module via the
Operator Interface
Ethernet based Unit Data Highway (UDH). All
The operator interface is commonly referred to analog and digital data in the Mark VI is acces-
as the Human Machine Interface (HMI). It is a sible for HMI screens including the high reso-
PC with a Microsoft® Windows NT® operating lution time tags for alarms and events.
system supporting client/server capability, a
System (process) alarms and diagnostics alarms
CIMPLICITY® graphics display system, a
for fault conditions are time tagged at frame
Control System Toolbox for maintenance, and a
rate (10/20/40 ms) in the Mark VI control and
software interface for the Mark VI and other
transmitted to the HMI alarm management sys-
control systems on the network. (See Figure 3.)
tem. System events are time tagged at frame
It can be applied as:
rate, and Sequence of Events (SOE) for contact
� The primary operator interface for
inputs are time tagged at 1ms on the contact
one or multiple units
input card in the Control Module. Alarms can
� �
GE Power Systems GER-4193A (10/00) 7
SPEEDTRONIC™ Mark VI Turbine Control System
be sorted according to ID, Resource, Device, made with password protection (5 levels) and
Time, and Priority. Operators can add com- downloaded to the Control Module while the
ments to alarm messages or link specific alarm process is running. All application software is
messages to supporting graphics. stored in the Control Module in non-volatile
flash memory.
Data is displayed in either English or Metric
engineering units with a one-second refresh Application software is executed sequentially
rate and a maximum of one second to repaint a and represented in its dynamic state in a ladder
typical display graphic. Operator commands diagram format. Maintenance personnel can
can be issued by either incrementing / decre- add, delete, or change analog loops, sequenc-
menting a setpoint or entering a numerical ing logic, tuning constants, etc. Data points can
value for the new setpoint. Responses to these be selected and “dragged” on the screen from
commands can be observed on the screen one one block to another to simplify editing. Other
second from the time the command was issued. features include logic forcing, analog forcing,
Security for HMI users is important to restrict and trending at frame rate. Application soft-
access to certain maintenance functions such as ware documentation is created directly from
editors and tuning capability, and to limit cer- the source code and printed at the site. This
tain operations. A system called “User includes the primary elementary diagram, I/O
Accounts” is provided to limit access or use of assignments, the settings of tuning constants,
particular HMI features. This is done through etc. The software maintenance tools (Control
the Windows NT User Manager administration System Toolbox) are available in the HMI and
program that supports five user account levels. as a separate software package for virtually any
Windows 95 or NT based PC. The same tools
Software Maintenance Tools are used for EX2000 Generator Excitation
Systems, and Static Starters. (See Figure 4 and
The Mark VI is a fully programmable control
Figure 5.)
system. Application software is created from in-
house software automation tools which select
Communications
proven GE control and protection algorithms
and integrate them with the I/O, sequencing,
Communications are provided for internal data
and displays for each application. A library of
transfer within a single Mark VI control; com-
software is provided with general-purpose munications between Mark VI controls and
blocks, math blocks, macros, and application peer GE control systems; and external commu-
specific blocks. It uses 32-bit floating point data nications to remote systems such as a plant dis-
(IEEE-854) in a QNX operating system with tributed control system (DCS).
real-time applications, multitasking, priority-
The Unit Data Highway (UDH) is an Ethernet-
driven preemptive scheduling, and fast context
based LAN with peer-to-peer communication
switching.
between Mark VI controls, EX2000 Generator
Software frame rates of 10, 20, and 40 ms are Excitation Controls, Static Starters, the GE
supported. This is the elapsed time that it takes Fanuc family of PLC based controls, HMIs, and
to read inputs, condition the inputs, execute Historians. The network uses Ethernet Global
the application software, and send outputs. Data (EGD) which is a message-based protocol
Changes to the application software can be with support for sharing information with mul-
� �
GE Power Systems GER-4193A (10/00) 8
SPEEDTRONIC™ Mark VI Turbine Control System
control. All trips between units are hardwired
even if the UDH is redundant.
The UDH communication driver is located on
the Main Processor Card in the Mark VI. This is
the same card that executes the turbine appli-
cation software; therefore, there are no poten-
tial communication failure points between the
main turbine processor and other controls or
monitoring systems on the UDH. In TMR sys-
tems, there are three separate processor cards
executing identical application software from
identical databases. Two of the UDH drivers are
normally connected to one switch, and the
Figure 4. Software maintenance tools – card
other UDH driver is connected to the other
configuration
switch in a star configuration. Network topolo-
gies conform to Ethernet IEEE 802.3 standards.
The GE networks are a Class “C” Private
Internet according to RFC 1918: Address
Allocation for Private Internets – February
1996. Internet Assigned Numbers Authority
(IANA) has reserved the following IP address
space 192.168.1.1: 192.168.255.255 (192.168/
Relay Ladder Diagram Editor
for Boolean Functions
16 prefix).
Communication links from the Mark VI to
remote computers can be implemented from
either an optional RS232 Modbus port on the
Figure 5. Software maintenance tools – editors
main processor card in Simplex systems, or
from a variety of communication drivers from
tiple nodes based on the UDP/IP standard
the HMI. When the HMI is used for the com-
(RFC 768). Data can be transmitted Unicast,
munication interface, an Ethernet card in the
Multicast or Broadcast to peer control systems.
HMI provides an interface to the UDH, and a
Data (4K) can be shared with up to 10 nodes at
second Ethernet card provides an interface to
25Hz (40ms). A variety of other proprietary
the remote computer.
protocols are used with EGD to optimize com-
munication performance on the UDH.
All operator commands that can be issued from
an HMI can be issued from a remote computer
40 ms is fast enough to close control loops on
through the HMI(s) to the Mark VI(s), and the
the UDH; however, control loops are normally
remote computer can monitor any application
closed within each unit control. Variations of
software data in the Mark VI(s). Approximately
this exist, such as transmitting setpoints
500 data points per control are of interest to a
between turbine controls and generator con-
plant control system; however, about 1,200
trols for voltage matching and var/power-factor
� �
GE Power Systems GER-4193A (10/00) 9
SPEEDTRONIC™ Mark VI Turbine Control System
points are commonly accessed through the � Additional “master” communication
communication links to support programming drivers are available from the HMI.
screen attributes such as changing the color of
a valve when it opens. Time Synchronization
Time synchronization is available to synchro-
Communication Link Options
nize all controls and HMIs on the UDH to a
Communication link options include:
Global Time Source (GTS). Typical GTSs are
� An RS-232 port with Modbus Slave Global Positioning Satellite (GPS) receivers
RTU or ASCII communications from such as the StarTime GPS Clock or other time-
the Main Processor Card. (Simplex: processing hardware. The preferred time
full capability. TMR: monitor data only sources are Universal Time Coordinated (UTC)
– no commands) or GPS; however, the time synchronization
option also supports a GTS using local time as
� An RS-232 port with Modbus Master /
its base time reference. The GTS supplies a
Slave RTU protocol is available from
time-link network to one or more HMIs with a
the HMI.
time/frequency processor board. When the
� An RS-232/485 converter (half-
HMI receives the time signal, it is sent to the
duplex) can be supplied to convert
Mark VI(s) using Network Time Protocol
the RS-232 link for a multi-drop
(NTP) which synchronizes the units to within
network.
+/-1ms time coherence. Time sources that are
� Modbus protocol can be supplied on
supported include IRIG-A, IRIG-B, 2137, NASA-
an Ethernet physical layer with TCP-IP
36, and local signals.
for faster communication rates from
the HMI.
Diagnostics
� Ethernet TCP-IP can be supplied with
Each circuit card in the Control Module con-
a GSM application layer to support the
tains system (software) limit checking, high/low
transmission of the local high-
(hardware) limit checking, and comprehensive
resolution time tags in the control to a
diagnostics for abnormal hardware conditions.
DCS from the HMI. This link offers
System limit checking consists of 2 limits for
spontaneous transmission of alarms
every analog input signal, which can be set in
and events, and common request
engineering units for high/high, high/low, or
messages that can be sent to the HMI
low/low with the I/O Configurator. In addition,
including control commands and
each input limit can be set for latching/non-
alarm queue commands. Typical
latching and enable/disable. Logic outputs
commands include momentary logical
from system limit checking are generated per
commands and analog “setpoint
frame and are available in the database (signal
target” commands. Alarm queue
space) for use in control sequencing and alarm
commands consist of silence (plant
messages.
alarm horn) and reset commands as
High/low (hardware) limit checking is provid-
well as alarm dump requests that cause
ed on each analog input with typically 2 occur-
the entire alarm queue to be
rences required before initiating an alarm.
transmitted from the Mark VI to the
These limits are not configurable, and they are
DCS.
� �
GE Power Systems GER-4193A (10/00) 10
SPEEDTRONIC™ Mark VI Turbine Control System
selected to be outside the normal control ing the correct termination point. One wire in
requirements range but inside the linear hard- each connector is dedicated to transmitting an
ware operational range (before the hardware identification message with a bar-code serial
reaches saturation). Diagnostic messages for number, board type, hardware revision, and a
hardware limit checks and all other hardware connection location to the corresponding I/O
diagnostics for the card can be accessed with card in the Control Module.
the software maintenance tools (Control System
Toolbox). A composite logic output is provided
Power
in the data base for each card, and another
In many applications, the control cabinet is
logic output is provided to indicate a high/low
powered from a 125Vdc battery system and
(hardware) limit fault of any analog input or
short circuit protected external to the control.
the associated communications for that signal.
Both sides of the floating 125Vdc bus are con-
The alarm management system collects and
tinuously monitored with respect to ground,
time stamps the diagnostic alarm messages at
and a diagnostic alarm is initiated if a ground is
frame rate in the Control Module and displays
detected on either side of the 125Vdc source.
the alarms on the HMI. Communication links
When a 120/240vac source is used, a power
to a plant DCS can contain both the software
converter isolates the source with an isolation
(system) diagnostics and composite hardware
transformer and rectifies it to 125Vdc. A diode
diagnostics with varying degrees of capability
high select circuit chooses the highest of the
depending on the protocol’s ability to transmit
125Vdc busses to distribute to the Power
the local time tags. Separate manual reset com-
Distribution Module. A second 120/240vac
mands are required for hardware and system
source can be provided for redundancy.
(software) diagnostic alarms assuming that the
Diagnostics produce an under-voltage alarm if
alarms were originally designated as latching
either of the AC sources drop below the under-
alarms, and no alarms will reset if the original
voltage setting. For gas turbine applications, a
cause of the alarm is still present.
separate 120/240vac source is required for the
Hardware diagnostic alarms are displayed on
ignition transformers with short circuit protec-
the yellow “status” LED on the card front. Each
tion of 20A or less.
card front includes 3 LEDs and a reset at the
top of the card along with serial and parallel
The resultant “internal” 125Vdc is fuse-isolated
ports. The LEDs include: RUN: Green; FAIL:
in the Mark VI power distribution module and
Red; STATUS: Yellow.
fed to the internal power supplies for the
Control Modules, any expansion modules, and
Each circuit card and termination board in the
the termination boards for its field contact
system contains a serial number, board type,
inputs and field solenoids. Additional 3.2A fuse
and hardware revision that can be displayed; 37
protection is provided on the termination
pin “D” type connector cables are used to inter-
board TRLY for each solenoid. Separate 120Vac
face between the Termination Boards and the
feeds are provided from the motor control cen-
J3 and J4 connectors on the bottom of the
ter for any AC solenoids and ignition trans-
Control Module. Each connector comes with
formers on gas turbines. (See Table 11.)
latching fasteners and a unique label identify-
� �
GE Power Systems GER-4193A (10/00) 11
SPEEDTRONIC™ Mark VI Turbine Control System
IEC 6100-4-4: 1995
Steady
Electrical Fast Transient Susceptibility
State Freq. Load Comments
IEC 6100-4-5: 1995
Voltage
Surge Immunity
125Vdc 10.0 A dc Ripple <= 10V p-p
(100 to Note 1 IEC 61000-4-6: 1995
144Vdc)
Conducted RF Immunity
120vac 47 - 63Hz 10.0 A rms Harmonic distortion < 5%
IEC 61000-4-11: 1994
(108 to Note 2
132vac)
Voltage Variation, Dips, and Interruptions
240vac 47 - 63 Hz 5.0 A rms Harmonic distortion < 5 %
ANSI/IEEE C37.90.1
(200 to Note 3
Surge
264vac)
Table 11. Power requirements
CE - Low Voltage Directive
EN 61010-1
Electrical Equipment, Industrial Machines
Codes and Standards
IEC 529
ISO 9001 in accordance with Tick IT by Lloyd's
Intrusion Protection Codes/NEMA 1/IP 20
Register Quality Assurance Limited. ISO 9000-
Reference the Mark VI Systems Manual GEH-
3 Quality Management and Quality Assurance
6421, Chapter 5 for additional codes and stan-
Standards, Part 3: Guidelines for the Appli-
dards.
cation of ISO 9001 to Development Supply and
Maintenance of Software.
Environment
Safety Standards
The control is designed for operation in an air-
conditioned equipment room with convection
UL 508A Safety Standard Industrial Control
cooling. Special cabinets can be provided for
Equip.
operation in other types of environments.
CSA 22.2 No. 14 Industrial Control Equipment
Temperature:
Printed Wire Board Assemblies
Operating 0° to +45°C +32° to +113°F
UL 796 Printed Circuit Boards
Storage -40° to +70°C -40° to +158°F
UL recognized PWB manufacturer,
The control can be operated at 50∞C during
UL file number E110691
maintenance periods to repair air-conditioning
ANSI IPC guidelines
systems. It is recommended that the electronics
ANSI IPC/EIA guidelines
be operated in a controlled environment to
maximize the mean-time-between-failure
CE - Electromagnetic Compatibility (EMC)
(MTBF) on the components.
EN 50081-2
Generic Emissions Standards
Purchased commercial control room equipment
EN 50082-2:1994
such as PCs, monitors, and printers are typically
Generic Immunity Industrial Environment
capable of operating in a control room ambient
EN 55011
of 0° to +40°C with convection cooling.
Radiated and Conducted Emissions
IEC 61000-4-2:1995
Humidity
Electrostatic Discharge Susceptibility
5% to 95% non-condensing
IEC 6100-4-3: 1997
Radiated RF Immunity
Exceeds EN50178: 1994
� �
GE Power Systems GER-4193A (10/00) 12
SPEEDTRONIC™ Mark VI Turbine Control System
Communication Links From HMI:
Elevation
RS232 Modbus Master/Slave, Ethernet
Exceeds EN50178: 1994
Modbus Slave, Ethernet TCP-IP GSM HMI
Gas Contaminants
SPEEDTRONIC™ Application Manual -
EN50178: 1994 Section A.6.1.4 Table A.2 (m)
Chapter 7 (GEH-6126), Ethernet TCP-IP
GEDS Standard
Dust Contaminants
Message Format (GSM) (GEI-100165)
Exceeds IEC 529: 1989-11 (IP-20)
� Operator/Maintenance Interface HMI
Seismic Universal Building Code (UBC)
HMI for SPEEDTRONIC™ Turbine
Section 2312 Zone 4
Controls
Application Manual (GEH-6126)
Documentation
Cim Edit Operation Manual (GFK-1396)
The following documentation is available for
Mark VI Turbine Controls. A subset of this doc-
User Manual (GFK-1180)
umentation will be delivered with each control
Cimplicity HMI For Windows NT
depending on the functional requirements of
Trending Operators
each system.
Manual (GFK-1260)
Manuals
� Turbine Historian System Guide
� System Manual for SPEEDTRONICTM
(GEH-6421)
Mark VI Turbine Control (GEH-6421)
� Standard Blockware Library (SBLIB)
� Control System Toolbox, for
� Turbine Blockware Library
Configuring a Mark VI Controller
(TURBLIB)
(GEH-6403)
Drawings
Configuring the Trend Recorder (GEH-
� Equipment Outline Drawing AutoCAD
6408)
R14
System Data Base for System Toolbox
� Equipment Layout Drawing AutoCAD
(GEI-100189)
R14
System Data Base Browser (GEI-100271)
� I/O Termination List (Excel
Data Historian (used for trip history)
Spreadsheet)
(GEI-100278)
� Network one-line diagram (if
� Communications To Remote
applicable)
Computers / Plant DCS
� Application Software Diagram
RS232 Modbus Slave From Control
(printout from source code)
Module
� Data List For Communication Link To
Modbus Communications
DCS
Implementation UCOC2000 - I/O
Drivers, Chapter 2
� �
GE Power Systems GER-4193A (10/00) 13
SPEEDTRONIC™ Mark VI Turbine Control System
List of Figures
Figure 1. Benefits of Speedtronic™ Mark VI
Figure 2. Mark VI TMR control configuration
Figure 3. Operator interface graphics: 7FA Mark VI
Figure 4. Software maintenance tools – card configuration
Figure 5. Software maintenance tools – editors
List of Tables
Table 1. Discrete I/O
Table 2. Analog I/O
Table 3. Temperature Monitoring
Table 4. VTUR I/O terminations from Control Module
Table 5. VPRO I/O terminations from Backup Protection Module
Table 6. VSVO I/O terminations from Control Module
Table 7. Nominal servo valve ratings
Table 8. VVIB I/O terminations from Control Module
Table 9. VGEN I/O terminations from Control Module
Table 10: VPYR I/O terminations from Control Module
Table 11: Power requirements
� �
GE Power Systems GER-4193A (10/00) 14
What they say about us
FANTASTIC RESOURCE
One of our top priorities is maintaining our business with precision, and we are constantly looking for affiliates that can help us achieve our goal. With the aid of GID Industrial, our obsolete product management has never been more efficient. They have been a great resource to our company, and have quickly become a go-to supplier on our list!
Bucher Emhart Glass
EXCELLENT SERVICE
With our strict fundamentals and high expectations, we were surprised when we came across GID Industrial and their competitive pricing. When we approached them with our issue, they were incredibly confident in being able to provide us with a seamless solution at the best price for us. GID Industrial quickly understood our needs and provided us with excellent service, as well as fully tested product to ensure what we received would be the right fit for our company.
Fuji
HARD TO FIND A BETTER PROVIDER
Our company provides services to aid in the manufacture of technological products, such as semiconductors and flat panel displays, and often searching for distributors of obsolete product we require can waste time and money. Finding GID Industrial proved to be a great asset to our company, with cost effective solutions and superior knowledge on all of their materials, it’d be hard to find a better provider of obsolete or hard to find products.
Applied Materials
CONSISTENTLY DELIVERS QUALITY SOLUTIONS
Over the years, the equipment used in our company becomes discontinued, but they’re still of great use to us and our customers. Once these products are no longer available through the manufacturer, finding a reliable, quick supplier is a necessity, and luckily for us, GID Industrial has provided the most trustworthy, quality solutions to our obsolete component needs.
Nidec Vamco
TERRIFIC RESOURCE
This company has been a terrific help to us (I work for Trican Well Service) in sourcing the Micron Ram Memory we needed for our Siemens computers. Great service! And great pricing! I know when the product is shipping and when it will arrive, all the way through the ordering process.
Trican Well Service
GO TO SOURCE
When I can't find an obsolete part, I first call GID and they'll come up with my parts every time. Great customer service and follow up as well. Scott emails me from time to time to touch base and see if we're having trouble finding something.....which is often with our 25 yr old equipment.
ConAgra Foods